User Manual

OPERATING THE AT10.1
43
Exercise front
panel controls
Switch from float to equalize, then back
to float.
Turn off the dc circuit breaker. E 07 may
appear on display (requires at least 5% of
rated output current). Reset breaker.
OK
OK
Cycle through meter modes.
VOLTS OK
AMPS OK
HOURS OK
Cycle through equalize methods.
MANUAL TIMER OK
MANUAL EQLZ OK
AUTO EQLZ TIMER OK
Turn off ac circuit breaker. The AC
INPUT FAILURE indicator should light.
Reset breaker.
Alarm OK
Check voltage
and alarm
settings
Use
EDIT/ENTER key to scroll through
settings. See page 30.
FLOAT OK
EQUALIZE OK
HVDC alarm OK
LVDC alarm OK
Current limit
Adc
Final checks
Make sure plexiglas safety cover is in
place.
Restore charger to normal operation.
Close latch on front panel.
OK
OK
OK
Step
(optional features)
Instructions Results
Test auxiliary
alarm relays
Press LAMP TEST key and hold for 4
seconds. Alarm relays will transfer.
OK
Check
integrity of
remote wiring
Remote sense wiring. See page 16.
Temperature compensation wiring. See
page 20.
Temperature compensation probe. See
page 20.
OK
OK
OK
Final checks
Close padlock or key lock.
OK
A downloadable worksheet of this Preventive Maintenance Procedure (JD0064-00)
is available online.