APPENDIX A: SCRFLX BATTERY CHARGERS. LIST OF DISPLAY INDICATIONS.
Indication Abbreviation Interpretation
1.00
1 hour delay set Delay before charge starts
2.00
2 hour delay set Delay before charge starts
3.00
3 hour delay set Delay before charge starts
4.00
4 hour delay set Delay before charge starts
5.00
5 hour delay set Delay before charge starts
6.00
6 hour delay set Delay before charge starts
8.00
8 hour delay set Delay before charge starts
CHP CHamPion
Control board is set to 2.55VPC not 2.70VPC.
COL COoL Down
Charger operates at Cool Down Stage
dEL dELay
Delay set or Charger operates at Delay Stage
End End
Charge Cycle complete
FAC or F3 Failure of AC power
Failure of mains
FCA Failure of DC CAble
disconnection
DC cable disconnected from the battery during the
charge
FCC
or
F2
Failure of Charge Cycle
Battery failed to reach Gassing Voltage (Stage 2)
or
Battery failed to reach End Voltage (Stage 3 of OPC)
FCd Failure of Cool down
Battery unplugged during Cool Down Stage
FdC Failure of dC Fuse
Output DC Fuse Failure
FFF FFatal Failure
Fatal Failure of the charger (Overvoltage or
Overcurrent protection or multifunction of Start Stop
signal)
FOC Failure of Overall Charge
timer
Overall charge cycle timer protection
FLd FLooded
Charger set for Flooded batteries
HI High Voltage Rejection
Battery connected has voltage more than 2.25VPC
LO LOw Voltage Rejection
Battery connected has voltage less than 1.70VPC
OFF OFF
Charger is OFF
rEJ rEJect
Battery connected has voltage too low or too high
or
Battery failed to reach 1.70VPC after 5 min of
charge
rFr reFreshing Stage
Charger operates at Refreshing Stage