Table 1. Programmable Parameter List
First Ke
y
Second Ke
y
Third Ke
y
Parameter(s) Descri
p
tion Allowable Settin
g
s Default Notes Locked
SET SET none none n/a n/a n/a
SET 1 (AMPS) None SA Set Amps 0.0-100.0 (A/100Ah) 0.0 3
SET 2 (VOLTS) None SV Set Volts 0.0-999.9 (V) 0.0 3
SET 3 (AH) None CR Cable Resistance 0-25 (m)2
SET START None
TS
DS
PS
EP
Time of Day Start
Delayed Start
Energy Management Peak Start
Ener
gy
Mana
g
ement Peak End
00:00-23:59; 99:99 (disable)
00:00-24:00 (hh:mm)
00:00-23:59; 99:99 (disable)
00:00-23:59; 99:99
(
disable
)
99:99
00:00
99:99
99:99
SET 4 (TOC) None ST Set Charge Time 00:00-99:99 (hh:mm) (99:99 runs forever) 00:00 3
SET 5 SET none n/a n/a n/a
SET 5 1 (AMPS) WA Watering Enable 0 (disable); 1 (every cycle); 2 (after equalize) 0
WC Watering Cycles 0-60 (15s ON/ 45s OFF) 0
SET 5 2 (VOLTS) CV Charge Cutoff Voltage 1.40-3.55 (v/c) 2.80 2
SET 5 3 (AH) EC Equalize by Number of Charges 0-100 7 2
ED Equalize by Day 0(disable); 1-7(Sun-Sat) 0 2
DE Equalize Delay Time 00:00-24:00 (hh:mm) 00:00 2
SET 5 START AL Charge Algorithm 1-17 n/a 1
SET 5 4 (TOC) VR Battery Voltage Rating 12-999 (V) 24
SET 5 5 (VER.) SR Charger Shunt Rating 0(current senso
r
); 50-600 (A) 200
SET 5 6 (I.D.) EM Equalize Mode 0 (None); 1(Normal) 1 2
EI Equalize Current 0.1-10.0 (A/100Ah) 5.0 2
SET 5 CLOC
K
MO Month 1-12 (Jan-Dec) n/a
DY Day (of the month) 1-31 n/a
YR Year 0-99 (years since 2000) n/a
SET 5 7 (TEMP)
CT
TU
Cool Down Time
Count U
p
/Down
00:00-24:00 (hh:mm)
0
(
count down
);
1
(
count u
p)
0:00
0
SET 5 8 (% RET.) AR Auto Refresh Time 00:00-72:00 (hh:mm) (0:00 disables) 0:00
SET 5 9 (80%) TP DVDT Trip Poin
t
1.20-2.55 (v/c) 2.38 2
SET 5 ENTER N2 F2 Indication Disable 0 (enable); 1 (disable) 1 2
N3 F3 Indication Disable 0 (enable); 1 (disable) 0 2
N4 F4 Indication Disable 0 (enable); 1 (disable) 0 2
N6 F6 Indication Disable 0 (enable); 1 (disable) 0 2
SET 5 = ET Equalize Time 00:00-24:00 (hh:mm) 3:00 2
SET 5 0 (TEST) AO Alert On Enable 0 (disable); 1 (enable) 1
AI Alert Interval 10-60 (s) 60
SET 5 STOP BC Battery Module Comm. Enable 0 (disable); 1 (enable); 2 (enable and upload alg.) 0
SET 6 (I.D.) None ID Charger I.D. (for Tobi or I'm Cool) 1-1000; 9999 9999
SET CLOC
K
none TD Time of Day (Clock) 00:00-23:59 (hh:mm) n/a
SET 7 (TEMP) none OT OK to Charge Temp 0-185 (˚F) (0 disables sensor) 0 2
LT
NT
Low Charge Temp
No Char
g
e Tem
p
0-185 (˚F)
0-185
(
˚F
)
115
125
2
2
SET 8 (% RET.) none CF Charge Back Facto
r
0-150 (% of AH rating) (0 disables) 120
SET 9 (80%) none MP Max Power Rating 0.1-25.0 (kW) 3.3 2
SET ENTER none custom alg. 1,2,3
SET = none CU DVDT Periods 0-15 (5 minutes each) 5
SET 0 (TEST) none BS Battery AH Rating 100-2200 (Ah) 0
SET STOP none AS Auto Start Mode 0 (manual start); 1 (auto star
t
); 2 (auto start on ac) 1
Notes:
1. The Algorithm is set for the particular charger and battery type. If you are unsure of which algorithm to use, consult factory before setting.
2. These parameters are part of the algorithm. Any changes made to these are overwritten whenever the algorithm parameter is set.
3. These parameters are only used for certain algorithms. Consult the factory before changing any unfamiliar parameters.