User Guide
  ZSME000000016 
7
EXCELL PRECISI
ON CO., LTD
2.4 Connections 
Two terminals are provided, labeled "Field cable” and “Instrument cable”. Field cable is the 
independent, exposed cable between the weighbridge and weighing cabin. Instrument or 
load cell cable is a locally short connection, such as from SP151 to the junction box, 
independent load cell or weighing scale. Equipments connected to the terminal are subject 
to SP151 protection. 
SP151 allows the 4-wire (SIG1, SIG2, EXC1, EXC2) or line 6 (SIG1, SIG2,EXC1, EXC2, 
SENSE1, SENSE2) as well as two isolated lines. The function of each terminal is clearly 
marked on the junction box.   
The isolated lines connected to field cables and instrumentation cables are not connected 
with the ground wire of the SP151 without affecting the ground operation of the general 
weighing system. 
If your vendor requires the isolated lines to be grounded, it should be connected to 
the junction box or load cell.   
Cable through the cable seal sleeve, stripped and attached to the corresponding 
connections are clearly marked and the subsequent failure detection would be easier. 
Ensure that the seal sleeve casing is tight, and then lock the lid. 
Figure 4 
SP151 
Field Cable
(Unprotected) 
Inst
rumentation 
or Cell Cable
AC  Power  feed
Weigh Computer 
Consumer Unit 
Earth/Ground 
Connection
*
Subsidiary earth 
bond if   
earth/ground link 
>3m/10ft