eWON Cosy 131 INSTALLATION GUIDE IG-0022-00 1.
Important User Information Liability Every care has been taken in the preparation of this document. Please inform HMS Industrial Networks SA of any inaccuracies or omissions. The data and illustrations found in this document are not binding. We, HMS Industrial Networks SA, reserve the right to modify our products in line with our policy of continuous product development.
Table of Contents 1 2 3 4 5 6 Page Preface ............................................................................................................................... 3 1.1 About This Document.....................................................................................................3 1.2 Document History ..........................................................................................................3 1.3 Related Documents ..................................................
Table of Contents B Specification of the External Power Supply........................................................... 22 C Digital Output & Digital Inputs ................................................................................... 23 C.1 Possible Features ........................................................................................................24 D Supported Wireless Wi-Fi Frequencies...................................................................
Preface 3 (26) 1 Preface 1.1 About This Document The present Installation Guide describes the hardware of the eWON Cosy 131 which is an industrial gateway / router fully compatible with the Talk2M cloud connectivity services. For additional related documentation and file downloads, please visit www.ewon.biz/support. 1.2 1.3 1.4 Document History Version Date Description 1.0 1.1 2015-01-22 2015-02-04 First release Modified: Multiples pictures 1.2 1.
Product Summary 4 (26) 2 Product Summary 2.1 Concept of the eWON Cosy 131 There are 4 models of the eWON Cosy 131, each proposing a different communication media: 2.2 2.
Safety, Environmental & Regulatory Information 3 Safety, Environmental & Regulatory Information 3.1 Scope 5 (26) This chapter addresses safety, environmental & regulatory information for the eWON Cosy 131. 3.2 Power Supply The external power supply is a third party device that is not part of this certification. The device shall be powered by an LPS power supply certified according to IEC/UL60950-1 or Class2 per NEC (for more information, refer to Specification of the External Power Supply, p. 22).
Safety, Environmental & Regulatory Information • 3.3.4 6 (26) This device must accept any interference received, including interference that may cause undesired operation. Certifications The product described in the present Installation Guide complies with part 15 of the FCC Rules.
Safety, Environmental & Regulatory Information Fig. 1 7 (26) DIN rail mounting position # Description 1 2 SIM card slot DIN rail mounting bracket Fig. 2 Wall mounting position # Description 1 2 SIM card slot DIN rail mounting bracket eWON Cosy 131 Installation Guide IG-0022-00 1.
Safety, Environmental & Regulatory Information 8 (26) To ensure a proper ventilation of the equipment, a free gap of at least 2 cm must be respected in front of all upper & lower ventilation openings of the unit. A free gap of at least 1 cm must be respected on each side of the unit. Fig. 3 3.4.3 Free gap surrounding the eWON for heat dissipation. Cabling Rules Shielded cables must be used for Ethernet and USB connectivity to comply with the EMC requirements.
Safety, Environmental & Regulatory Information 3.4.
Hardware Description 10 (26) 4 Hardware Description 4.1 Label The identification label of the eWON Cosy 131 is placed on the right hand side of the housing.
Hardware Description 11 (26) The following table explains the Part Number syntax: EC6133m_ccLL[suffix] 4.
Hardware Description 12 (26) 4.3 Overall Description 4.3.1 Front 4.3.2 # Description 1 2 3 Reset button Status LEDs LAN / WAN Ethernet ports and corresponding status LEDs (Red: WAN and Green: LAN) 4 5 USB slot SD card slot Fig. 6 Front panel Fig. 7 plug Main connector and associated Upper Side # Description 1 Main connector including power input terminal,1 DO and 2 DI For more information about the connector, refer to Main Connector, p.
Hardware Description 4.3.3 13 (26) Status LED All Versions Label Description BI1 Button BI1 input Steady green = reset button is being pressed PWR Power Steady green = unit is powered on USR User Blinking green slowly = Unit is ok Red pattern = special attention required KEY Digital IN 1 See Digital Output & Digital Inputs, p. 23 Green = ON : Signal on Input 1 detected DI2 Digital IN 2 See Digital Output & Digital Inputs, p.
Hardware Description 4.4 14 (26) Radio Communication Models This device is intended to be used in fixed or mobile applications only (not for portable applications). The antenna used for this transmitter has to be installed in a space providing a safe distance of at least 20 cm without encountering anyone and must not be collocated or operating in conjunction with any other antenna or transmitter. 4.4.1 eWON Cosy 131 with Internal Wi-Fi Model Item Value(s) Protocols and frequencies IEEE802.
Hardware Description 4.4.
Hardware Description 4.4.
Hardware Description 17 (26) 4.5 LAN Switch Specifications 4.5.1 Boot Process After powering on or requesting a reboot of the eWON Cosy 131, a wait is required to get the LAN switch feature fully operational. (approximately 45 sec). The ultimate decision the eWON takes when it can no more run a given configuration is to reboot itself. This aims at restoring the requested communication channels and being consistent with the requested configuration. 4.5.
IP Address & Access to the Web Configuration 18 (26) 5 IP Address & Access to the Web Configuration 5.1 Factory Default IP Settings Characteristics LAN IP address LAN subnet mask Gateway Values 10.0.0.53 255.255.255.0 0.0.0.0 Since firmware version 10, the WAN IP address is set by default in DHCP mode. 5.2 Powering On Power on the unit and wait approximately 45 seconds until the boot process is completed. After a successful boot process the USR LED is blinking green slowly.
Troubleshooting 19 (26) 6 Troubleshooting 6.1 Normal Boot Process The normal boot process of the eWON Cosy 131 takes approximately 25 seconds to complete. During this process, all LEDs are first shortly on (except BI1) then only the PWR LED stays steady green. As soon as the boot process is completed and the unit is ready to be used, the USR LED blinks green slowly whereas others might be steady green (if the device is connected to Internet, Talk2M...). 6.
Troubleshooting 20 (26) • Check if the auto test is successful, the USR LED blinks red with a pattern of 200ms on and 1500ms off. The eWON does NOT restart by itself in normal mode and remains running in this diagnostic mode. • Power off the eWON and power it on again to reboot the unit in a normal mode. As described before, the eWON returns to its default COM parameters and factory IP addresses (such as LAN 10.0.0.53) after this level 2 reset is performed. Any other LED pattern reflects a problem.
Appendix A: Connector Pinout & Related Specifications 21 (26) A Connector Pinout & Related Specifications A.1 Main Connector As shown in the below picture, the female mating connector is labeled with the appropriate symbols. Characteristic Connector type Value MINICONNEC MC model Type MC 1.5 / 9–ST-3.5 Pitch = 3.50mm 9–pin female Maximal tightening torque 0.
Appendix B: Specification of the External Power Supply B 22 (26) Specification of the External Power Supply The eWON Cosy 131 must be powered by a safety Low Power Supply (LPS) in accordance with clause 2.5 of UL/IEC 60950-1 Ed2. Standard, 12-24Vdc, 30W min. Certified for 60°C and for altitudes up to 2000m. The safety LPS power supply is not part of the delivery. Suggested power supply : SIEMENS SITOP logo power 24V 2.5A 60W - Siemens order ref: 6EP1332-1SH43. Equivalents are available on the market.
Appendix C: Digital Output & Digital Inputs C 23 (26) Digital Output & Digital Inputs Fig. 13 Current scheme of the main connector Characteristic Type of digital output 6 Value Open drain MOSFET Maximum current (ext,source) 200 mA Isolation (both DI & DO) 1.
Appendix C: Digital Output & Digital Inputs Fig. 14 C.1 24 (26) External wiring for the Digital Output Possible Features Wiring the Digital Output & Inputs can be used to externalize some features (as connectivity condition) as described below: LED Connector Description KEY DI1 to authorize or prevent the Internet connection to authorize or prevent the VPN connection DI2 DI2 Not implemented T2M DO Can be wired to an external device to propagate the Talk2M status.
Appendix D: Supported Wireless Wi-Fi Frequencies D 25 (26) Supported Wireless Wi-Fi Frequencies Fig. 15 Supported Wi-Fi frequencies Supported channels frequencies are between channel 1 (2,412 Ghz) and channel 11 (2,462 Ghz). Channels 12, 13 & 14 are not supported eWON Cosy 131 Installation Guide IG-0022-00 1.
last page © 2017 HMS Industrial Networks AB Box 4126 300 04 Halmstad, Sweden info@hms.se IG-0022-00 1.9.