Code version 1.14
FEATURE
DEFAULT
RANGE TO SELECT
System Type
HP Type
T-Stat Type
Rev Valve
Fan Mode
Heat/Cool
NON
Dual Fuel
RV ‘O’
Hydro
OAS SP
15°
O.T. Offset
15°
8°
U.T. Offset
SAS HP TGT
SAS Gas TGT
SAS Cool TGT
100°
125°
50°
PURGE FAN
SAS RSP DLY
W2 Threshold
30s
85%
25%
Heat Pump or Heat/Cool
Dual Fuel or Non-Dual Fuel
Heat Pump or Heat/Cool
‘O’ Type RV or ‘B’ Type RV
GAS or HYDRO (Electric)
OFF or 7° to 42° F.
5° to 20° F.
5° to 10° F.
90° to 120° F.
120° to 170° F.
42° to 60° F.
10seconds - 180seconds
65% - 100% (Adj. in 5 point increments)
25% - 100% (Adj. in 25 point increments)
Heat/Cool
Total Zones
3
2 or 3 zones
25%, 50%, 75% or 100%
Legacy DMD
75%
Limit SAS
PID
Yes or No
N
1. Legacy Demand feature allows the Installer to select the weight value of 24v non-communicating zones.
2. Total Zones feature allows the Installer to select the exact number of zones, which changes the PID quotient value.
3. Limit SAS PID sets a limit to the PID loop highest attainable value at the sum of the pro-rated thermostat value.