Product Overview

Table Of Contents
SUBMITTAL SHEET
TM
Forced Air Zone Controls
Model PS4
EBD (Static Pressure Switch)
The PS4 is used to sense the static pressure in the supply
air duct and maintain the static pressure set point limit
that the system will operate at. The PS4 will control an ND
or URD damper, to allow an adequate amount of pressure
to by-pass from the supply plenum to the return duct or
dump zone, and maintain design static pressure and
velocity. The PS4 has a range of 0.1" to 4.0" W.C. The PS4
can be used with motor actuators to create model EBD by-
pass dampers.
Adjustment of the Switch
After mounting the pitot tube and diaphragm in a suitable location (The pressure switch should be
mounted with the graduated stem in a vertical position. The pressure switch cannot be mounted
sideways or upside-down), connect the tubing from the pitot tube, to the high pressure tap on the
diaphragm. Use the barb connector as shown. Leave the low pressure tap open to atmosphere. (See
drawing on page 2). Wire the PS4 to the bypass damper as shown on page 2. Remove cover from
diaphragm switch to make your field connections. Make sure the zone system is operating properly
and all zone dampers are in the open position. Power up the bypass damper assembly. Unscrew and
remove the cap on the PS4 diaphragm. Turn the static pressure adjusting screw up or down until the
top of the screw lines up with the static pressure scale setting you require. (Factory setting is .5”
W.C.) Observe that the bypass damper should be closed when all zone dampers are open. If the
bypass damper is open or partially open, adjust the set point for a higher static. Then, start to close
off one or more zone dampers and observe the bypass damper as the static pressure control senses
the increased air pressure and modulates the bypass damper open or closed to maintain the static
pressure set point you require.
Package includes:
1 - Pressure Diaphragm
1 - 3/8” barb connector
1 - wiring harness
1 - Mounting bracket
1 - Bolt/washer
1 - Pitot tube
1 - 8’ length tubing
2 - wire connectors
6 -1/4” screws
Note: The pressure switch should be mounted as close to vertical as possible to ensure proper
operation.
®
385 Hwy. 33
Englishtown, NJ 07726
Ph: 800-446-3110
Fx: 732-446-5362
P/N 090377A0063 REV.H 10.30.09
CONTROLS INC.
E
W
Excellence Without Compromis
e
Copyright © 2000, EWC Controls Inc., All Rights Reserved
SUBMITTAL FORM
SUBMITTED BY:
JOB:
ARCHITECT:
ENGINEER:
CONTRACTOR:
LOCATION: