Product Overview
Model URD
w/ MA-ND4 Actuator
The URD series of round motorized dampers are a double layered blade design with an 
integrated cellular foam sealing gasket. The superior design insures long life and no 
maintenance. URD dampers are easy to install, easy to wire up, and come with a 5 year 
warranty. The URD damper is constructed of heavy gauge galvanized steel. The nylon 
bearings and drive shafts insure smooth, quiet operation and provides a thermal barrier to 
the motor. It is designed to operate at static pressures up to 1” w.c. @ < 3% leakage.
The UL Listed Motor Actuator is a 24vac 3 wire power open / power close type rated at 18 “ 
lbs. of torque. It includes an integrated terminal block, and NEMA1 rated housing. The MA-
ND4 motor features bright Green and Red LED's which correspond to the OPEN and 
CLOSED position of the blade. The motor also includes End Stops for Min/Max position 
capability to allow adjustment of the design CFM flow into a particular zone or area (See 
figure below). The Position LED’s will illuminate regardless of the Min/Max settings. A 
positional arrow is also included that provides visual indication of blade travel. The 
Damper should be installed to orient motor at any angle top or sides. Do not install with 
motor at bottom of the duct work. 
MODEL #  A  B
NOMINAL DIMENSIONS
4.00”
10.00”
12.00”
12.00”
12.00”
12.00”
12.00”
5.00”
6.00”
7.00”
8.00”
9.00”
10.00”
12.00”
14.00”
16.00”
14.00”
URD - 4
URD - 5
URD - 6
URD - 7
URD - 8
URD - 9
URD - 10
URD - 12
URD - 14
20.00”
16.00”
URD - 16
10.00”
B
A
Positional Indicator
not attached for clarity
SUBMITTAL SHEET
E
wC
Excellence Without Comprimise
CONTROLS INC.
MA-ND4
24 VAC 50/60Hz 1.5VA 1W
18 in-lb (2Nm) 35s
MANUAL
GEAR
RELEASE
!
Class2
Supply
CLOSED
OPEN
0 1
PC
PO
COM
1 4 6
0 1
END STOP ADJUSTMENT
-LOOSEN PHILIPS
 HEAD SCREW 
-MOVE END-STOP 
 TO DESIRED POSITION
-TIGHTEN PHILIPS
 HEAD SCREW
20.00”
18.00”
URD - 18
20.00”
20.00”
URD - 20
385 Hwy. 33 
Englishtown, NJ 07726
Ph: 800-446-3110 
Fx: 732-446-5362
P/N 090377A0068 REV. L
CONTROLS INC.
E
W
Excellence Without Compromis
e
Copyright © EWC Controls 2005 - 2008 All Rights Reserved
SUBMITTAL FORM
SUBMITTED BY:
JOB:
ARCHITECT:
ENGINEER:
CONTRACTOR:
LOCATION:
Forced Air Zone Controls
®