Product Overview
Installing the Bypass Damper and Static 
Pressure Control Assembly:
The bypass damper should be installed  with  the 
bypass air being discharged back into the return air 
plenum or above the ceiling if this area is used as a 
common return.
 (See drawing). 
Mount the pitot tube within 5 feet of the air handling 
unit,  down  stream  of  the  By-Pass  duct,  on  the 
center  line  of  a  straight  section  of  supply  duct 
(Observe  direction  of  airflow  arrow  stamped  on 
pitot tube mounting plate).   The pitot tube is a 5” 
length of 1/4" O.D. rigid tubing to be connected to 
the pressure control with 3/8" O.D. plastic tubing, 
The  High-pressure  tap  of  the  static  pressure 
control must be connected to the pitot tube. The 
Low-pressure  tap  must  be  left  open  to 
atmosphere.  Keep  the  3/8”  plastic  tubing  as 
short as possible with no kinks. The pitot tube, 
plastic  tubing,  and  mounting  hardware  are 
furnished with the Bypass Damper assembly.
Adjusting the Static Pressure Control:
Before  adjusting  the  pressure  control,  the  installer 
should confirm the following:
(1) The HVAC System is functioning properly.
(2) The system has been properly balanced.
(3) The zone system is operating properly.
(4) All zone dampers are in the open position.
How To Proceed:
With the air handler running at the highest speed & full 
CFM rating and the bypass damper system powered, 
turn the static pressure adjusting screw until the top of 
the screw aligns with the static pressure scale setting 
you require. (Factory setting is .5” W.C.) Observe that 
the bypass damper should be closed when all zone 
dampers are open. If it’s open or partially open, adjust 
the set point for a higher static. Then, start to close off 
one or more zone dampers and observe as the static 
pressure control senses the  increased air pressure 
and modulates the bypass damper, to maintain the 
set point you have chosen.  
385 Hwy. 33 Englishtown, NJ 07726
Ph: 800-446-3110 - Fx: 732-446-5362
CONTROLS INC.
Excellence Without Compromis
e
E
W
C
TM
Forced Air Zone Controls
Note: This drawing of the Bypass damper static pressure control and related duct work is intended to serve only as a guide, 
your actual duct work layout may differ substantially.
Bypass Damper and Static Pressure Control Assembly
HVAC
UNIT
Return air Supply air
Pitot Tube
Static Pressure
 Control
24 Volt 40 VA 
Transformer
or
UltraZone Control
Panel
 Damper
 Motor
 By-Pass 
 Damper
Model EBD
Electronic By-Pass Damper
6’
6’
Note: The pressure switch should be mounted as close to vertical as possible to ensure proper operation.
Use 3/8” O.D.
Plastic tubing
P/N 090377A0061 REV. I 04.08.10