User Guide

Table Of Contents
Model ND
w/ MA-ND4 Actuator
Insertion Mounting
Cut a 4” slotted opening in one side of the duct and slide the damper in. Secure the damper to the
duct with the supplied sheet metal screws. Larger sizes may require additional support by securing the
back of the damper as well. If using duct board, additional support can be obtained by using Model
DBA Duct Board Adaptors.
*If flush wall mounting is required, cut the flanges off of the front mounting plate.
MOTOR Terminal Output
M6 - Power to Close (PC)
M4 - Power to Open (PO)
M2 - Constant Power (HOT)
M1 - Common (COM)
Wiring to a Control Panel
M6
M4
M2
M1
6-PC
1-COM
4-PO
Motor
Wiring in Parallel
M6
M2
M1
M4
WIRING SOLUTIONS
GYW R
SYSTEM
COOL
OFF HEAT
AUTO
ON
FAN
JUMPER
C
H
EWT THERMOSTAT
w/TSB-M SUB-BASE
or
EQUIVALENT
TRANSFORMER
24VAC, T-40VA
or
EQUIVALENT
R1 RELAY SPDT
w/24VAC COIL
or
EQUIVALENT
COM-1
PO-4
PC-6
Motor
Wiring a Thermostat to Control a Single Damper
Conventional
Thermostat
NO CONNECTION
Motor
6-PC
1-COM
4-PO
Motor
6-PC
1-COM
4-PO
Motor
6-PC
1-COM
4-PO