Evolve Series ® Water Filters For Models: • EVFE • EVS • EAG • EACG • EVBF • EVBF-AN
TABLE OF CONTENTS Preinstallation Instructions for Dealers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Bypass Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7 Programming Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PREINSTALLATION INSTRUCTIONS FOR DEALERS: The manufacturer has preset the water treatment unit’s sequence of cycles and cycle times. The dealer should read this page and guide the installer regarding day override, time of regeneration, service alarm and buzzer alarm settings before installation. For the installer, the following must be used: • Program Installer Settings ... Day Override (preset to 3 days), Time of Regeneration (preset to 12:00 a.m.
BYPASS VALVE: The bypass valve is typically used to isolate the control valve from the plumbing system’s water pressure in order to perform control valve repairs or maintenance. The 1” full flow bypass valve incorporates four positions, including a diagnostic position that allows a service technician to have pressure to test a system while providing untreated bypass water to the building. Be sure to install bypass valve onto main control valve, before beginning plumbing.
INSTALLATION: GENERAL INSTALLATION & SERVICE WARNINGS The control valve, fittings and/or bypass are designed to accommodate minor plumbing misalignments. There is a small amount of “give” to properly connect the piping, but the water softener is not designed to support the weight of the plumbing. Do not use Vaseline, oils, other hydrocarbon lubricants or spray silicone anywhere. A silicone lubricant may be used on black “O” Rings, but is not necessary.
When installing an air regenerating filter the customer may experience, under certain conditions, small amounts of air (cloudy water) at the taps. This is normal. On rare occasions, this may result in “shots of air” at a particular fixture. By installing a loop or “U” on the outlet side of the unit, this will act as an air trap and improve this situation. (Air charge models only) Located inside the inlet is an internal check valve (see diagram at right).
8. CHECK VALVE: All air systems include an internal check valve and screen assembly as part of the air draw system (see diagram at right). This check valve, screen, and elbow are exclusive to the air system and are not to be confused or interchanged with a brine elbow used on a softener. The gray color of the elbow indicates use with an air system vs. a black elbow which indicates use with a water softeners.
PROGRAMMING PROCEDURES: 1. Set time of day: Time of day should only need to be set after extended power outages or when daylight saving time begins or ends. If an extended power outage occurs, the time of day will flash on and off indicating that the time should be reset. STEP 1 – Press SET CLOCK. STEP 2 – CURRENT TIME (HOUR): Set the hour of the day using + or — buttons. AM/PM toggles after 12. Press NEXT to go to step 3. STEP 3 – CURRENT TIME (MINUTES): Set the minutes using + or — buttons.
NOTE: This valve has the capability of regenerating up to six times in one day. This can be observed by pressing the CLOCK and + buttons simultaneously, then using + or — buttons to toggle the correct number of regenerations per day as desired (see example to right). Press NEXT to set the times per day or select “OFF” to return to Days Between Regen. These settings are typically used in commercial settings. Press NEXT to go to step 4. Press NEXT to go to step 5. Press REGEN NEXT to go to step 6.
START-UP INSTRUCTIONS: FLUSHING OF SYSTEM: To flush the system of any debris and air after installation is complete, please perform the following steps: 1. Rotate bypass handles to the bypass mode (see Fig. 2 of page 4). 2. Turn on inlet water and check for leaks in the newly installed plumbing. 3. Fully open a cold water faucet, preferable at a laundry sink or bathtub without an aerator. 4. Wait two to three minutes or until water runs clear, then turn water off and follow start-up instructions.
OPERATING DISPLAYS AND INSTRUCTIONS: The air sulfur and air iron filter systems look and function much like any backwashing whole house filter; however, unlike these conventional filters, they use air as a regenerant. This atmospheric air (containing oxygen) helps convert iron or hydrogen sulfide into particles. These filters capture the particles of iron or hydrogen sulfide gas within the filter media. Your dealer has recommended the proper media depending on your local water conditions.
4. MANUAL REGENERATION: Sometimes there is a need to regenerate before the control valve calls for it. This may be needed if a period of heavy water use is anticipated. • To initiate a manual regeneration at the next preset regeneration time, press and release REGEN. The words “REGEN TODAY” will flash on the display to indicate that the system will regenerate at the next regeneration time (set in Programming, steps 4 and 5).
REPLACEMENT MINERAL INSTRUCTIONS FOR ACID NEUTRALIZERS: The EACG Iron Filter/Acid Neutralizer will remove iron and also raise the pH of mildly acidic water. The EVAN Upflow Acid Neutralizer will raise the pH of acidic water. The raising of pH utilizes a sacrificial mineral that will need replenishment every 6 to 12 months. Typically the media should not be below the halfway point in the tank. In order to check the mineral height and before adding mineral to the system, please follow these instructions. 1.
TROUBLESHOOTING GUIDE: PROBLEM 1. No display on PC board 2. PC board does not display correct time of day 3. Display does not indicate that water is flowing. Refer to user instructions for how the display indicates water is flowing. 4. Control valve regenerates at wrong time of day 5. Time of day flashes on and off CAUSE CORRECTION A. No power at electric outlet A. Repair outlet or use working outlet B.
PROBLEM 7. Control valve does not regenerate automatically but does when the correct button(s) is depressed and held. For timeclock valves the buttons are ▲ & ▼. For all other valves the button is REGEN. 8. Hard or untreated water is being delivered 9. Control valve uses too much regenerant 10. Residual regenerant being delivered to service 11. Excessive water in regenerant tank CAUSE CORRECTION A. Bypass valve in bypass position A. Turn bypass handles to place bypass in service position B.
TROUBLESHOOTING GUIDE cont’d: PROBLEM 12. Control valve fails to draw in regenerant 13. Water running to drain 14. E1, Err – 1001, Err – 101 = Control unable to sense motor movement 15. E2, Err – 1002, Err – 102 = Control valve motor ran too short and was unable to find the next cycle position and stalled CAUSE CORRECTION A. Injector is plugged A. Remove injector and clean or replace B. Faulty regenerant piston B. Replace regenerant piston C. Regenerant line connection leak C.
PROBLEM 15. E2, Err – 1002, Err – 102 = Control valve motor ran too short and was unable to find the next cycle position and stalled CAUSE CORRECTION D. Improper voltage being delivered to PC board D. Verify that proper voltage is being supplied. Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect. E. Valve type is programmed incorrectly E. Verify valve body and program PC board to match A.
TROUBLESHOOTING GUIDE cont’d: PROBLEM CAUSE CORRECTION 19. Err – 1007, Err – 107, Err - 117 = MAV/ SEPS/NHBP/AUX A. Foreign material is lodged in MAV valve motor MAV/NHBP valve ran too short (stalled) while looking for proper park position A. Open up MAV/NHBP valve and check piston and seal/ stack assembly for foreign material. Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.
REPLACEMENT PARTS: FRONT COVER AND DRIVE ASSEMBLY Item No. 1 Part No. CV3367-01-A Description Qty.
REPLACEMENT PARTS: 1 13 14 5 9 4 7 3 8 10 2 11 PISTON ASSEMBLY Item No. Part No. Description Qty. CV3005 1” spacer stack assembly 1 CV3430 1.25” spacer stack assembly 1 2 CV3004 Drive cap assembly 1 3 CV3135 O-ring 228 1 CV3011 1” piston assembly downflow 1 1 4 1” piston assembly upflow 1 CV3407 1.25” piston assembly downflow 1 5 CV3174 Regenerant piston 1 6 CV3180 O-ring 337 1 CV3105 O-ring 215 1 CV3358 O-ring 219, 1.
REPLACEMENT PARTS: BYPASS VALVE Item No. Part No. 1 2 3 4 5 6 7 8 9 10 CV3151 CV3150 CV3105 CV3145 CV3146 CV3147 CV3148 CV3152 CV3155 CV3156 Description Qty.
REPLACEMENT PARTS: INJECTOR ASSEMBLIES Item No. Part No.
REPLACEMENT PARTS: DRAIN LINE ASSEMBLY 3/4” Item No. Part No. 1 CH4615 2 CPKP10TS8-BULK 3 CV3192 4 CV3158-02 5 CV3163 6 7 8 CV3159-01 Description Elbow locking clip 1 Optional insert, 5/8” tube 1 Optional nut, 3/4” drain elbow 1 Drain elbow, 3/4” NPT with O-ring 1 O-ring 019 1 DLFC retainer assembly 1 CV3162-007 0.7 DLFC for 3/4” elbow CV3162-010 1.0 DLFC for 3/4” elbow CV3162-013 1.3 DLFC for 3/4” elbow CV3162-017 1.7 DLFC for 3/4” elbow CV3162-022 2.
REPLACEMENT PARTS: WATER METER & METER PLUG Item No. Part No. Description Qty. 1 CV3151 Nut, 1” QC 1 2 CV3003 Meter assembly, includes items 3 & 4 1 3 CV3118-01 4 CV3105 5 CV3003-01 Meter plug assembly 1 6 CV3013 Optional mixing valve 1 Turbine assembly 1 O-ring 215 1 SERVICE WRENCH - CV3193-02 Although no tools are necessary to assemble or disassemble the valve, the Service Wrench, (shown in various positions on the valve) is available to aid in assembly or disassembly.
REPLACEMENT PARTS: CHLORINE TANK ASSEMBLY Item No. Part No. Description Qty.
INSTALLATION FITTING ASSEMBLIES: 1” PVC MALE NPT ELBOW Item No. 1 2 3 4 Part No. Description CV3007 CV3151 CV3150 CV3105 CV3149 1” PVC male NPT elbow assembly Nut, 1” quick connect Split ring O-ring 215 Fitting 3/4” & 1” PVC SOLVENT ELBOW Item No. Qty. 2 2 2 2 2 1 2 3 4 1” BRASS SWEAT Item No. 1 2 3 4 Part No. CV3007-02 CV3151 CV3150 CV3105 CV3188 Description 1” brass sweat assembly Nut, 1” quick connect Split ring O-ring 215 Fitting 1 2 3 4 Part No.
1-1/4” & 1-1/2” BRASS SWEAT Item No. 1 2 3 4 1-1/4” & 1-1/2” PVC SOLVENT Part No. Description Qty. CV3007- 09 CV3151 CV3150 CV3105 CV3375 1-1/4 & 1-1/2” brass sweat assembly Nut, 1” quick connect Split ring O-ring 215 Fitting 2 2 2 2 2 Item No. 1 2 3 4 3/4” BRASS SHARK BITE Item No. 1 2 3 4 Part No. CV3007-12 CV3151 CV3150 CV3105 CV3628 Description 3/4” brass Shark Bite assembly Nut, 1” quick connect Split ring O-ring 215 Fitting Part No. Description Qty.
SPECIFICATIONS: SULFUR AND IRON AIR FILTERS MODEL NUMBER EVS-1054 EVS-1248 EVS-1354 EVFE-1054 EVFE-1248 EVFE-1354 Mineral Type Amount (Cu Ft) Catalytic Carbon 1.0 Catalytic Carbon 1.5 Catalytic Carbon 2.0 Birm 1.0 Birm 1.5 Birm 2.0 Gravel Amount/Size (No. 1) Gravel Amount/Size (No. 2) 14 lb 1/4 x 1/8 7 lb #20 21 lb 1/4 x 1/8 7 lb #20 21 lb 1/4 x 1/8 7 lb #20 14 lb 1/4 x 1/8 7 lb #20 21 lb 1/4 x 1/8 7 lb #20 21 lb 1/4 x 1/8 7 lb #20 Continuous Flow (GPM) 1 Peak Flow (GPM) 5.0 20.0 6.
ACID NEUTRALIZERS MODEL NUMBER EVBF-1044AN Mineral Type Amount (Cu Ft) Gravel Amount/Size (No. 1) Gravel Amount/Size (No. 2) Continuous Flow (GPM) Peak Flow (GPM) Backwash Flow (GPM) EVBF-1054AN EVBF-1354AN EVAN-1044 EVAN-1054 EVAN-1354 Calcite or Mix 1.0 Calcite or Mix 1.5 Calcite or Mix 2.5 Calcite or Mix 1.0 Calcite or Mix 1.5 Calcite or Mix 2.
Evolve Series® Water Conditioner Limited Warranty Congratulations. You have purchased one of the finest water treatment systems available.
QUICK REFERENCE GUIDE: GENERAL OPERATION MANUAL REGENERATION When the system is operating, one of six displays will be shown: 1. time of day/gpm 2. flow rate 3. vacation mode 4. capacity remaining 5. days to a regen 6. dealer name and phone number NOTE: For softeners, if brine tank does not contain salt, fill with salt and wait at least two hours before regeneration.
ADJUST HARDNESS, DAYS BETWEEN REGENERATION, TIME OF REGENERATION AND ALARM BUZZER For initial set-up or to make adjustments, please complete the following steps. 1. Accessed by pressing NEXT and + button simultaneously 2. Adjust hardness using + and — buttons 3. Press SERVICE ALARM GAL NEXT SET 4. Adjust days between regenerations using + and — buttons 5. Press NEXT 6. Adjust time of regeneration hour with + and — buttons, AM/PM toggles at 12. 7.