d. Press the ON/OFF button on the remote controller. The water pump will start when the
time reaches the TIMER ON setting and the heat pump will start 60 seconds after this
value. The heat pump will shut down when it reaches the TIMER OFF value and the
water pump will shut down 30 seconds afterwards . Actual conditions can be checked
by going to the MAIN menu and selecting UNIT status to view water inlet and outlet,
refrigerant pipe and ambient air temps.
e. With the water pump running, check for water leakage and check for optimum water
ow. Adjust water ow by adjusting bypass valves until water ow through heater is
sufcient.
f. After the unit runs for a few minutes, check whether the air discharged by the fan is
noticeably cooler than the ambient air. Another way to determine if the heater is working
correctly is to view MAIN MENU>UNIT STATUS. Check to see if the WATER OUT temp
is higher than the WATER IN temp. If no cold air check or the water in and out temps
are the same check the refrigerant gauge on the heater to ensure there is a refrigerant
charge in the unit. Check also the INLET WATER TEMP is lower than the HEAT TEMP
set point.