Specifications
12
d. Then press the ON/OFF button on the remote controller. The heater will start shortly
after water ๎
ow commences. Actual conditions can be checked by going to the MAIN
menu and selecting UNIT status to view water inlet and outlet, refrigerant pipe and
ambient air temps.
e. After the unit runs for a few minutes, check whether the air discharged by the fan is
noticeably cooler than the ambient air. If no cold air check the refrigerant gauge on the
heater to ensure there is a refrigerant charge in the unit. Another way to determine if
the heater is working correctly is to view MAIN MENU>UNIT STATUS. Check to see if
the WATER OUT temp is higher than the WATER IN temp. If no cold air or the water in
and out temps are the same check the refrigerant gauge on the heater to ensure there
is a refrigerant charge in the unit. Check also the INLET WATER TEMP is lower than the
HEAT TEMP set point.
f. Turn the water pump off while the unit is running. The unit should stop working
automatically and a water ๎
ow error will appear. If not, contact Evo Industries
for further advice.
g. Turn the water pump on again and wait for the unit to restart.
3.8b Initial start up at handover
METHOD 2 - HEAT PUMP CONTROLS THE WATER PUMP
a. Check the connections, wires and cables of the unit are correctly installed.
b. Turn on the power to the heater at the main isolating switch. With the heater in
STANDBY mode, enter the MAIN menu and select HEAT. ESC back to the ๎rst menu
screen and select the PARAMETER menu and adjust the HEAT TEMP to 30 degrees
(adjust higher if the pool water temp is hotter than 30 degrees). Go to the PUMP
sub-menu in the PARAMETER menu and change to SPECIAL.
c. Go to the TIME sub-menu and set the current day and time. Set the TIMER ON to a
value 5mins in the future and the TIMER OFF value 10mins in the future.