Technical data
USB AND RS232 COMMUNICATION
10000 series units are equipped with extended management functions. There are two RS232 and
USB communication ports and PowerSoft Personal software provided with the UPS. To ensure correct
communication, it is necessary to connect the UPS to a free computer port with the provided communication
cable. Once connected, the UPS and computer should be switched on and the software should be installed as
per the enclosed manual and by following the installation application's instructions (applies to
SINLINE PRO
Microsoft
Windows).
SNMP/HTTP NETWORK MANAGEMENT CARD
The EVER network management card is optional and can be installed by the user. It is a device that is used to
integrate the UPS with an Ethernet-type computer network. The network card is located in the special slot on the
back wall of the UPS. The card enables the user to manage the UPS from any computer in the network. This
solution is most often used for central power supply, or if there is a need to manage the power supply system
remotely. The management card features the following services:
SNMP agent enables power supply management with software called
SNMP manager;
HTTP server enables the display and modification of the UPS parameters by using a web
Browser;
EPO
EPO (Emergency Power Off) is a mechanism that cuts off the energy supply to receivers at the UPS output in
extreme situations (e.g. a fire).
The mechanism can be activated in two ways:
- disconnected pins of the external EPO connector (release device),
- manual command on the interface (CONTROL 1/3; EmergencyShut-down).
The output voltage will be circuited again after the user commands the cancellation of the alert flag (CONTROL
2/3; EraseFailure) and sets the release device to inactive (normal position) - in case of the external initiation of the
release. It is possible to temporarily lock the EPO function during the assembly of the EPO release device. Then,
the technician can remove the EPO connector without risking a blackout of the receiver devices. It may last up to 1
minute, beginning from the setting of the control flag (CONTROL 2/3, Shut-down time.EPO). After that time, the lock is
automatically turned off.
The unit switches to EMERGENCY mode.
NOTE! A connected SNMP card UPS communication with RS232, USB, and
PowerSoft Personal.
enables
!
SERVICE BYPASS SWITCH
The unit is equipped with a service BYPASS line switch, which enables the direct
switching of the BYPASS line to connect it to the output clips of the unit and
bypassing the unit blocks.
www.ever.eu
SINLINE PRO 10 000