Technical data

SINLINE PRO 10 000
GENERAL DATA
PARAMETERS
SINLINE PRO 10 000
1)
Output power
Topology
VI
10 kVA
8 kW
>98 %>98 %
IP20
Separate room with low contamination level
Forced, internal fans
Total efficiency for Pmax AC/AC
Protection level
Work environment
2)
Working temperature
Storage temperature
Relative humidity when working
Relative humidity during storage
Input voltage
Output voltage (RMS)
Output voltage waveform
Output voltage frequency
Input voltage frequency
Input voltage range
Switching thresholds: mains-ups
Switching thresholds: Ups-mains
Output voltage filtering
Output voltage distortion THDu
Crest factor CF
Short circuit current
Output voltage waveform
Output voltage filtering
3)
Altitude above sea level
Cooling
10
0
÷40 C
0
0
÷40 C
< 95 %
< 95 %
< 1000 m
~150÷280 V (~165÷280 V)± 2 %
~172,5÷252 V (~190÷252 V)± 2 %
~230 V ± 2 %
< 5 % for Pmax (line)
2:1
>4:I
N
Sine
LC
~150 V/~290 V (~165 V/~280 V) ± 2 %
~155 V/~285 V (~170 V/~275 V) ± 2 %
Synchronous / 50Hz ± 0.2 Hz
The same as the input
RFI/EMI interference filter, varistor muffler
45 ÷ 55 Hz ± 1 Hz
POWER NETWORK MODE
BATTERY MODE
TECHNICAL DATA
Notes:
1)
2)
3)
For standard operation, the load that is applied to the output must not exceed 80% of the value in the table.
The power margin is necessary to ensure the continuous work of the connected devices in the case of instantaneous surges of the load.
Constant exposure of the battery module to temperatures of +25°C reduces the battery life.
The permitted maximum load of the power supply unit decreases with the height above the sea level above the limit specified above.
Note: The manufacturer reserves the right to modify the above parameters without prior notice.