Specifications

SCF-050 Manual
29
Fi
g
ure 14
the Furnace is put back in service, (Defective Room Fan, dirty Room Fan, dirty
Return Air Filter, defective Fan Limit Control or possibly a bad Control Board)
2. Proof of Fire switch also called the P.O.F. This senses the temperature rise in the
exhaust system. The switch is “Normally Open” and closes the circuit at 110
degrees. The Furnace will shut down if temperatures above 110 degrees F are not
sensed during start up or if the temperature drops below 110 degrees during
normal operation.
3. Vacuum switch also called the Negative pressure switch. When the Furnace is
turned on the Exhaust fan will create a negative pressure in the firebox. The
control board continually checks to see if Negative Pressure (vacuum) is present
during operation of the Furnace. If the exhaust venting system becomes clogged
or obstructed, the firebox door or ash pan door are left open or the exhaust fan
quits working the control board will go into “Safety shutdown”. There is a 60
second window to allow for cleaning the glass and removing the clinker before
then Furnace shuts down. This is sufficient for the Daily Maintenance
The SCF-050 has been Safety Tested by an accredited, independent laboratory.
Combustion Air Damper
Do not neglect to
adjust the
Combustion Air damper during the
break in period of your new Furnace
(See Figure 14 to the left). Your
Furnace is equipped with an air inlet
damper. The purpose of this damper
is to adjust combustion airflow to
match the characteristic of each
specific air inlet and chimney
configuration. The damper is preset
at the factory with a setscrew. The
damper will most likely only need a
small adjustment during the break in
period. To know if the damper needs
to be adjusted you should learn to
recognize how Corn, wheat or rye or
Pellets burn in this furnace system.