EVD120 Summary Summary [ EVD120 ] Important Important ............................................................................................................................................................. 5 Introduction Introduction ......................................................................................................................................................... 7 Getting started 1 Getting started ..............................................................................
EVD120 Important [ EVD120 ] Important Important Read these instructions carefully before installing and using the instrument and follow all additional information for installation and electrical connection; keep these instructions close to the instrument for future consultations. The instrument must be disposed according to the local legislation about the collection for electrical and electronic equipment.
EVD120 Introduction [ EVD120 ] Introduction Introduction EVD120 is a two analog channels and two digital inputs acquisition module. Each analog channel can work with one of the following kind of probe (universal analog channels): • PTC/NTC probe • J/K thermocouple • 2/3 wires Pt 100 and Pt 1000 probe • 2/3 wires 4-20 mA passive current transducer • 0-10/2-10 V and 0-20/4-20 mA active transducer.
EVD120 Getting started [ EVD120 ] Getting started 1 Getting started 1.1 Installing the instrument On DIN rail; dimensions in mm (in). Fig. 1 - Dimensions of EVD120. Fig. 2 - Installation of EVD120. Additional information for installation: • working conditions (working temperature, humidity, etc.) must be between the limits related in the technical data • do not install the instrument close to heating sources (heaters, hot air ducts, etc.
EVD120 Getting started 1.2 Wiring diagram Fig. 3 - Wiring diagram of EVD120. With reference to the wiring diagram: • port 1 is the port for the serial communication (via RS-485, with MODBUS communication protocol) • port 2 is the serial port for the communication with the programming key.
EVD120 Programming [ EVD120 ] Programming 2 Programming 2.1 Preliminary remarks EVD120 supports the MODBUS communication protocol. The kind of network EVD120 can work in is RS-485 (look at Fig. 4); for further information on the realization of the network, consult the Installation manual of RICS for Windows® (the document is available in the CD of RICS). According to the standard settings: • the instrument address has value 247 • the baud rate has value 9,600 baud • the parity has value even.
EVD120 Programming (3) gain access to RICS with the • operate the remaining connections related in paragraph 1.2 • connect the power supply of the instruments in the network • start RICS (3) (4) . account of the administrator or of the Keep operating as follows: installer 1. Quit possible dialog boxes. (4) 2. Right-click on the desktop, then use the quick menu to choose Add Device. the availability of the functions A new picture will be shown.
EVD120 Programming 14. Choose Exit, then Exit again. 15. Switch off the power supply of EVD120. 16. Disconnect terminals “1”, “2” and “3” of EVD120 from the RS-485 output of the serial interface. 2.
EVD120 Programming • press the button of EVKEY 1 s: LED Prog of EVD120 will flash and the LED of EVKEY will shed green light and • press and release the button of EVKEY: the LED of EVD120 will go out; if the LED of EVKEY sheds green light red light alternatively (6) consider value 0, if it sheds red light consider value 1 (6) the value to consider is not the instrument address; the instrument address is the sum of all the values to consider in the procedure • press and release the button of EV
EVD120 Programming • press and release the button of EVKEY: LED Power/Status and LED Communication of EVD120 will light up; if the LED of EVKEY sheds green light consider value 0, if it sheds red light consider value 64 (6) • press and release the button of EVKEY: all the LED of EVD120 will light up; if the LED of EVKEY sheds green light consider value 0, if it sheds red light consider value 128 (6) • press and release the button of EVKEY: the procedure will be quitted, LED Prog of EVD120 will flash an
EVD120 Programming 2.6 Copying the configuration parameters of EVD120 in the programming key EVKEY using the software Params Manager Operate as follows: • make sure to have the programming key EVKEY • switch on the power supply of EVD120 and wait 4 s at least since the power supply has been switched on • connect EVKEY to port 2 of EVD120: the LED of EVKEY will shed green light Fig. 5 - Connecting EVKEY to port 2 of EVD120.
EVD120 Programming 2.
EVD120 Configuration parameters [ EVD120 ] Configuration parameters 3 Configuration parameters 3.1 Preliminary remarks Configuration parameters are visible using one of the following software: • RICS • Params Manager. 3.2 (11) if parameters “Probe kind 1” Configuration parameters TEXT FIELD MIN. MAX. U.M. DEF.
EVD120 Configuration parameters 10 = 2 wires Pt 1000 11 = 4-20 mA 12 = 0-20 mA 13 = 2-10 V 14 = 0-10 V (13) the unit of measure depends on Probe1 Offset -25.0 25.0 (13) 0.0 offset analog channel 1 parameters “Celsius Fahrenheit” (°C Probe2 Offset -25.0 25.0 (13) 0.0 offset analog channel 2 or °F) and “Probe kind 1” or “Probe DigitalFilter probe 1 0 6 --- 3 reading speed analog channel 1 (0 = fast ...
EVD120 Configuration parameters TEXT FIELD MIN. MAX. U.M. DEF.
EVD120 Signals [ EVD120 ] Signals 4 Signals 4.1 LED Power/Status If it is lit, the instrument will be supplied. If it flashes, an analog channel 1 error and/or an analog channel 2 error will be running. Remedies: • look at parameters “Probe kind 1” and/or “Probe kind 2” • check the integrity of the probe • check the connection instrument-probe • check the variable read by the probe. If it is out, the instrument will not be supplied. 4.
EVD120 Signals If it flashes, the instrument will read some data but it will not be the recipient. Remedies: • look at parameters “instrument address” of the instruments of the RS-485 network. If it is mainly out, the instrument will read some not correct data. Remedies: • look at parameters “baud rate” and “parity” of the instruments of the RS-485 network. If it is out, the serial communication will not be running. 4.
EVD120 Technical data [ EVD120 ] Technical data 5 Technical data 5.1 Technical data Box: self-extinguishing grey. Frontal protection: IP 40. Connections: • screw terminal blocks (power supply, inputs and port for the serial communication) • 6 poles connector (port for the communication with the programming key). Working temperature: from 0 to 55 °C (32 to 131 °F, 10 ... 90% of relative humidity without condensate). Power supply: 230 VAC, 50/60 Hz, 1.5 VA (approximate).
User manual of EVD120. Version 1.00 of November 2006. File EVD120_user_manual_eng_v1.00.pdf. PT. This document belongs to Evco; unless you are authorized by Evco, you can not publish it. Evco does not take any responsibility about features, technical data and possible mistakes related in this document or coming by its use. Evco does not take any responsibility about damages coming by the non-observance of the additional information.
MODBUS/JBUS IMPLEMENTATION TABLE Applied to the following products: EVD120 File name: ModBUS_PRJ314AA06_v1.02.pdf Version: 1.
Evco S.r.l. 1 INTRODUCTION This document describes the resources of the device that can be accessed via the serial port. The protocol is MODBUS RTU/JBUS.
Evco S.r.l. Holding register addresses table: Address (zero based) Description Access Notes DIGITAL INPUTS Digital inputs register $0101 R Bit0 = Digital input 1 Bit1= Digital input 2 PROBES Probe 1 (1) $0201 R 1 decimal digit Probe 2 (1) $0202 R 1 decimal digit (1) Probes Reserved Value Meaning $8000 Probe failure $8001 Data not available ModBUS PRJ314AA06 v1.
Evco S.r.l. Address (zero based) Description Access Notes PARAMETERS Meas. unit (0 = Celsius, 1 = Fahrenheit) $0601 R/W Modbus nodes address $0610 R/W Baud Rate $0611 R/W Parity $0612 R/W Enable Auto-incremental address $0613 R/W Kind of digital input 1 (0 = NO, 1 = NC) $061F R/W msk $0001 = digital In 1 msk $0002 = digital In 2 bit0 bit1..3 bit4..7 bit8..11 bit12..
Evco S.r.l. Max range of linear input 2 (corresponding to 20 mA or 10 V) $0633 R/W Default 1000 $0634 R/W 0 = no saturation 1 = saturation on min and max range of linear input 2 2 = saturation on 0, 1000 3 = saturation on 0, 10000 Firmware ID $FF08 R Firmware Variation/revision $FF09 R Kind of saturation of linear input 2 INFO (2) Digital filter: 3 is the default value.
Evco S.r.l. ULTERIORI HOLDING REGISTER PER USO INTERNO FOTOGRAFIA SULLO STATO DELLO STRUMENTO: Tramite questi Holding Register è possibile eseguire una fotografia statica sul funzionamento dello strumento; in tale fotografia vengono riportati i valori misurati dalle sonde, il minimo e il massimo assunto da entrambe dal momento del precedente rinfresco, all’attuale lettura, lo stato degli ingressi digitali e degli allarmi, la traccia di una loro eventuale attivazione o disattivazione precedente.
Evco S.r.l.
Evco S.r.l. bit9: analogical input changed bit10: digital input changed bit11: analogical output changed bit12: digital input changed bit13: parameters value changed bit14:set point or other internal settings changed bit 15: reserved ModBUS PRJ314AA06 v1.