EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Vcolor 818 Controller for “top-class” blast chillers, with colour touch-screen TFT graphic display, in split version and which can be integrated into the unit ENGLISH INSTALLER MANUAL ver. 1.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Important Important Read this document thoroughly before installation and before use of the device and follow all recommendations; keep this document with the device for future consultation. The following symbols support reading of the document: indicates a suggestion indicates a warning. The device must be disposed of in compliance with local Standards regarding the collection of electric and electronic equipment.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Index 1 INTRODUCTION ...................................................................................................................................5 1.1 Introduction ........................................................................................................................................5 1.2 Summary table of the main features and the models available ..............................................................
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 7.2 Memorisation of a program ................................................................................................................. 51 7.3 Execution of a program ....................................................................................................................... 52 8 “FAVOURITES” FUNCTION .................................................................................................................
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 1 INTRODUCTION 1.1 Introduction Vcolor 818 is a controller with elegant design for the management of “top-class” blast chillers. It is available in split version and can be integrated both mechanically and aesthetically in the unit; the user interface consists of a colour touch-screen TFT graphic display and guarantees an IP65 protection rating, for easy cleaning.
EVCO S.p.A. 1.2 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Summary table of the main features and the models available The following table illustrates the main features of the device. “ / “ indicates the feature can be set via a configuration parameter. User interface (open frame) Vcolor 818 128.0 x 94.5 mm (5.039 x 3.720 in; L x H) • TFT graphic display 3.5 (inch) touch-screen with 16 colors and 240 x 320 pixel resolution Control module (open frame) • Vcolor 818 166.0 x 116.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Analogue outputs (PWM) Vcolor 818 evaporator fan (1) Digital outputs (electromechanical relays; A res.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 2 DESCRIPTION 2.1 Description of the user interface The following drawing illustrates the aspect of the Vcolor 818 user interface. The following table illustrates the meaning of Vcolor 818 user interface parts. Part Meaning 1 Interactive keys and display 2 USB serial port For further information, see the next chapters.
EVCO S.p.A. 2.2 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Description of the control module The following drawing illustrates the aspect of the Vcolor 818 control module. The following table illustrates the meaning of the Vcolor 818 control module parts.
EVCO S.p.A. 16 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 communication port with the user interface (signal and power supply) For further information, see the next chapters.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 3 DIMENSIONS AND INSTALLATION 3.1 User interface dimensions The following drawing illustrates the Vcolor 818 user interface dimensions; these are expressed in mm (in). 3.2 Control module dimensions The following drawing illustrates the Vcolor 818 control module dimensions; these are expressed in mm (in). 3.
EVCO S.p.A. 3.5 - Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Installation warnings make sure that the device work conditions (temperature of use, humidity, etc.) lie within the limits indicated; see chapter 16 "TECHNICAL DATA" - do not install the device near to any heat sources (heating elements, hot air ducts etc.), equipment containing powerful magnets (large diffusers, etc), areas affected by direct sunlight, rain, humidity, excessive dust, mechanical vibrations or shocks.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 4 ELECTRIC CONNECTION 4.1 Electric connection The following drawing illustrates the Vcolor 818 electric connection. The utility managed by the K7 output, depends on parameter u11, as follows: - cabinet light (u11 = 0, pre-defined setting) - UV light (u11 = 1). For the settings relative to the parameters, see chapter 11 “CONFIGURATION”.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 The RS-485 port is for the connection of the controller to the following additional products: - Parameters Manager set-up software system - Plant monitoring and supervision system via Internet: CLOUDEVOLUTION - printing module PM 100A X9S001. The port must not be used simultaneously with more than one of these products. 4.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 5 USER INTERFACE 5.1 Foreword The following operating status exist: - the “off” status (the device is not powered) - the “stand-by” status (the device is powered and is off) - the “on” status (the device is powered, is on and is in stand-by for the start-up of an operating cycle) - the “run” status (the device is powered, is on and an operating cycle is in progress).
EVCO S.p.A. 3. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the ON/STAND-BY key (1) and then press the highest interactive key on the left (2) to unlock the keyboard. 4. Press and release the ON/STAND-BY (1) key. If the duration of the power cut has been such to cause the clock error (“rtc” code), the real day and time will have to be reset; see paragraph 11.1 “Setting the real day and time”. 5.3 Switching the device on/off Operate as follows: 1.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 During the "run" state the device will display: - if a temperature-controlled blast chilling or deep freezing operation is in progress, the temperature detected by the needle probe, the temperature of the cabinet, the name of the program, (if envisioned) and the time passed from the start of blast chilling or deep freezing.
EVCO S.p.A. 5.5 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Display of inputs and outputs status Operate as follows: 1. Make sure that the instrument is in the “on” status. 2. Make sure that the keyboard is not locked and that no procedure is in progress. 3. Press and release the HOME key (1), press and release the MENU key (2) and then press and release the key repeatedly (3) in order to select the “INTERNAL VALUES”. 4.
EVCO S.p.A. 5.6 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Defrosting activation in manual mode Operate as follows: 1. Make sure the device is in the "on" status, that pre-cooling or storage cycle is in progress. 2. Make sure that the keyboard is not locked and that no procedure is in progress. 3. Press and release the key (1), press and release the key (2) and then press and release the START/STOP (3) key. If the evaporator probe is enabled, i.e.
EVCO S.p.A. 5.8 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Silencing the buzzer Operate as follows: 1. Make sure no procedures are in progress 2. Press and release the key.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 6 OPERATION 6.
EVCO S.p.A. 6.2 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Temperature-controlled blast chilling and storage The temperature-controlled blast chilling and storage cycle is divided into the following two phases: - blast chilling - storage. On conclusion of a phase, the device passes automatically to the next. Operate as indicated to start the cycle: 1. Make sure the device is in the "on" status. 2. Make sure that the keyboard is not locked and that no procedure is in progress. 3.
EVCO S.p.A. 5.1 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 If the test is completed successfully, the cycle will be started. The maximum blast chilling duration count is started on condition that the temperature detected by the needle probe is below that established with parameter r15. 5.2 If the test is not completed successfully, the buzzer will be activated for 5 s every 60 s and the cycle will be started with timed-control; see paragraph 6.
EVCO S.p.A. 6.3 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Temperature-controlled hard blast chilling and storage The temperature-controlled hard blast chilling and storage cycle is divided into the following three phases: - blast chilling hard phase - blast chilling - storage. On conclusion of a phase, the device passes automatically to the next. Operate as indicated to start the cycle: 1. Make sure the device is in the "on" status. 2.
EVCO S.p.A. 5. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the START/STOP key (1): the test to verify the correct insertion of the needle probe will be started; see paragraph 6.14 " Test for verification of the correct insertion of the needle probe". 5.1 If the test is completed successfully, the cycle will be started.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Parameter r10 establishes the work set-point during storage. If the temperature detected by the needle probe does not reach the blast chilling end temperature within the maximum blast chilling duration, blast chilling will not be completed successfully but will continue and the buzzer will be activated. Press and release a key to restore normal display and to silence the buzzer.
EVCO S.p.A. 4.1 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the MENU key and then press and release the key (4) or the key (5) to select the blast chilling duration and the work set-point during blast chilling. 4.2 Press and release the key + (6) or the key – (7) to modify these values and then the ESCAPE key to memorise them; these values can also be memorised through parameters r1 and r7. 5. Press and release the START/STOP key (1): the cycle will be started.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 During storage the device displays the temperature of the cabinet, the program name (if envisioned) and the duration of blast chilling. Parameter r10 establishes the work set-point during storage. 6.5 Time-controlled hard blast chilling and storage The time-controlled hard blast chilling and storage cycle is divided into the following three phases: - blast chilling hard phase - blast chilling - storage.
EVCO S.p.A. 4.2 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the key + (6) or the key – (7) to modify these values and then the ESCAPE key to memorise them; these values can also be memorised through parameters r1 and r7. 5. Press and release the START/STOP key (1): the cycle will be started.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Parameter r10 establishes the work set-point during storage. 6.6 Continuous blast chilling Operate as indicated to start the cycle: 1. Make sure the device is in the "on" status. 2. Make sure that the keyboard is not locked and that no procedure is in progress. 3. Press and release the key (1), press and release the key (2) and then press and release the key (3) twice.
EVCO S.p.A. 5. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the START/STOP key (1): the cycle will be started. During blast chilling the device displays the temperature of the cabinet, the program name (if envisioned) and the time passed since the start of blast chilling. Operate as indicated to stop the cycle: 6. Press and hold the START/STOP key 3 s. Parameter r7 establishes the work set-point during blast chilling. 6.
EVCO S.p.A. 4.1 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the MENU key and then press and release the key (4) or the key (5) to select the deep freezing end temperature and the work set-point during deep freezing. 4.2 Press and release the key + (6) or the key – (7) to modify these values and then the ESCAPE key to memorise them; these values can also be memorised through parameters r4 and r8. 5.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 If the temperature detected by the needle probe reaches the deep freezing end temperature within the maximum deep freezing duration, it means that deep freezing has been completed successfully, the device will automatically pass to storage and the buzzer will be activated for the period of time established with parameter AA. Press and release a key to silence the buzzer.
EVCO S.p.A. 6.8 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Temperature-controlled soft deep freezing and storage The temperature-controlled soft deep freezing and storage cycle is divided into the following three phases: - deep freezing soft phase - deep freezing - storage. On conclusion of a phase, the device passes automatically to the next. Operate as indicated to start the cycle: 1. Make sure the device is in the "on" status. 2.
EVCO S.p.A. 5.1 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 If the test is completed successfully, the cycle will be started. The maximum deep freezing duration count is started on condition that the temperature detected by the needle probe is below that established with parameter r15. 5.2 If the test is not completed successfully, the buzzer will be activated for 5 s every 60 s and the cycle will be started with timed-control; see paragraph 6.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 If the temperature detected by the needle probe does not reach the deep freezing end temperature within the maximum deep freezing duration, deep freezing will not be completed successfully but will continue and the buzzer will be activated. Press and release a key to restore normal display and to silence the buzzer.
EVCO S.p.A. 4.1 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the MENU key and then press and release the key (4) or the key (5) to select the deep freezing duration and the work set-point during deep freezing. 4.2 Press and release the key + (6) or the key – (7) to modify these values and then the ESCAPE key to memorise them; these values can also be memorised through parameters r2 and r8. 5. Press and release the START/STOP key (1): the cycle will be started.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 During deep freezing the device displays the temperature of the cabinet, the program name (if envisioned) and the duration of deep freezing. Parameter r11 establishes the work set-point during storage. 6.10 Time-controlled soft deep freezing and storage The time-controlled soft deep freezing and storage cycle is divided into the following three phases: - deep freezing soft phase - deep freezing - storage.
EVCO S.p.A. 4.1 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the MENU key and then press and release the key (4) or the key (5) to select the deep freezing duration and the work set-point during deep freezing. 4.2 Press and release the key + (6) or the key – (7) to modify these values and then the ESCAPE key to memorise them; these values can also be memorised through parameters r2 and r8. 5. Press and release the START/STOP key (1): the cycle will be started.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Parameter r11 establishes the work set-point during storage. 6.11 Continuous deep freezing Operate as indicated to start the cycle: 1. Make sure the device is in the "on" status. 2. Make sure that the keyboard is not locked and that no procedure is in progress. 3. Press and release the key (1), press and release the key (2) and then press and release the key (3) twice.
EVCO S.p.A. 5. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the START/STOP key (1): the cycle will be started. During deep freezing the device displays the temperature of the cabinet, the program name (if envisioned) and the time passed since the start of deep freezing. Operate as indicated to stop the cycle: 6. Press and hold the START/STOP key 3 s. Parameter r8 establishes the work set-point during deep freezing.
EVCO S.p.A. 6.12 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Blast chilling/deep freezing intensity The device can manage the phase cut speed regulator for EVDFAN1 single phase fans (to be ordered separately); see paragraph 15.1 “phase cut speed regulator for EVDFAN1 single phase fans”. The regulator can be used to manage evaporator fan activities with a single analogue control, i.e.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 speed 1... 5 (can be memorised with the procedure given Deep freezing - - in paragraph speed 5 6.12.
EVCO S.p.A. 6.12.1 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Selecting the evaporator fan speed Operate as follows: 1. Make sure the device is in the "on" status. 2. Make sure that the keyboard is not locked and that no procedure is in progress. 3. Press and release the key (1), press and release the key (2), and then press and release the key (3) or the key (4).
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Operate as follows to exit the procedure: 8. Press and release the ESCAPE key or do not operate for 60 s. The fan is switched on at the selected speed after 5 s from release of the key (1) or the key (2). 6.13 Pre-cooling start-up Every operating cycle can be preceded by pre-cooling. Operate as indicated to start pre-cooling: 1. Make sure the device is in the "on" status. 2.
EVCO S.p.A. 6.14 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Test for verification of the correct insertion of the needle probe If the needle probe is enabled, i.e. the parameter P3 is set at values different to 0; the temperature-controlled cycles are preceded by a test on two phases for the verification of the correct insertion of the needle probe. The second phase is only performed if the first is not completed successfully.
EVCO S.p.A. 5. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the key light (2) and then press and release the START/STOP key (3) The device will display the residual time of the UV light switch-on duration and the cabinet temperature. The UV light is switched on for the time period established by parameter u6; opening the door i.e. the activation of the door micro switch cause the light to switch off.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Output K6 is activated at maximum for the time established with parameter u8 or until the temperature detected by the needle probe reaches that established with parameter u7; closing the door, i.e. the deactivation of the door micro switch input causes heating to be cut-off. The buzzer is activated for 2 s on conclusion of heating. 6.
EVCO S.p.A. 4 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the key (4) or the key (5) to select these values and press and release the key + (6) or the key - (7) to modify them. 5. Press and release the START/STOP key (3): the test to verify the correct insertion of the needle probe will be started; see paragraph 6.14 " Test for verification of the correct insertion of the needle probe". 5.1 If the test is completed successfully, the cycle will be started. 5.
EVCO S.p.A. 6.18 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Data print-out The device can manage the PM 100A X9S001 module (to be ordered separately); see paragraph 14.5 "Print module PM 100A X9S001”. Using the module, it is possible to print information relative to the cabinet temperature, the temperature detected by the needle probe, at the alarms and at the errors (the latter two on condition that the alarm and/or the error is in progress on expiry of the print interval.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 7 “PROGRAMS” FUNCTION 7.1 Foreword The programs function can be used to memorise some settings in a program and start an operating cycle with the settings it has memorised. Up to 9 programs can be memorised. 7.2 Memorisation of a program Operate as follows: 1. Make sure that the keyboard is not locked and that no procedure is in progress. 2.
EVCO S.p.A. 3. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the key (2) or the key (3) to select the program number and then press and release the key SET (6) in order to associate a name. 4. Press and release the key (2), the key (3), the key (5) or the key (4) to select the character and then press and release the SET (6) key to confirm it. 5.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 8 “FAVOURITES” FUNCTION 8.1 Foreword The favourites function can be used to execute a recently started program. It is possible to start up to 9 recently started programs 8.2 Execution of a program Operate as follows: 1. Make sure the device is in the "on" status. 2. Make sure that the keyboard is not locked and that no procedure is in progress. 3.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 9 “HACCP” FUNCTION 9.1 Foreword Using the “HACCP” function, it is possible to memorise up to 9 events for each of the 3 HACCP alarms, after which the most recent event overwrites the oldest. The following table illustrates the information relative to the HACCP alarms, which the device can memorise.
EVCO S.p.A. 9.2 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Display of information relative to the HACCP alarms Operate as follows: 1. Make sure the device is in the "on" status. 2. Make sure that the keyboard is not locked and that no procedure is in progress. 3. Press and release the HOME key (1), press and release the MENU key (2) and then press and release the key (3) in order to select the “HACCP”. 4.
EVCO S.p.A. 9.3 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Deleting the information relative to the HACCP alarms Operate as follows: 1. 2. 3. Make sure the device is in the "on" status. Make sure that the keyboard is not locked and that no procedure is in progress. Press and release the HOME key (1), press and release the MENU key (2) and then press and release the key (3) in order to select the “HACCP”. 4.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 10 COMPRESSOR OPERATING HOURS COUNT 10.1 Display of compressor operating hours Operate as follows: 1. Make sure that the instrument is in the “on” status. 2. Make sure that the keyboard is not locked and that no procedure is in progress. 3. Press and release the HOME key (1), press and release the MENU key (2) and then press and release the key repeatedly (3) in order to select the “INTERNAL VALUES”. 4.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 11 CONFIGURATION 11.1 Setting the real day and time Operate as follows: 1. Make sure that the instrument is in the “on” status. 2. Make sure that the keyboard is not locked and that no procedure is in progress. 3. Press and release the HOME key (1) and then press and release the MENU key (2). 4.
EVCO S.p.A. 11.2 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Setting the configuration parameters Operate as follows: 1. Make sure that the instrument is in the “on” status. 2. Make sure that the keyboard is not locked and that no procedure is in progress. 3. Press and release the HOME key (1), press and release the MENU key (2) and then press and release the key repeatedly (3) in order to select the “PARAMETERS”. 4.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 11.3 Restoring the factory settings 11.3.1 Access to the procedure Operate as follows: 1. Make sure that the instrument is in the “stand-by” status. 2. Make sure that the keyboard is not locked and that no procedure is in progress. 3. Press and release the top right corner of the screen (1).
EVCO S.p.A. 11.3.3 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Deleting programs Operate as follows: 1. 2. Access to the; see paragraph 11.3.1 “Access to the procedure”. Press and release the key (1) to select “Programs”, repeatedly press and release the + key (2) to set “149” and then press and release the SET key (3). Operate as follows to exit the procedure: 3. Press and release the ESCAPE key or do not operate for 60 s. 11.3.4 Deleting favourites Operate as follows: 1.
EVCO S.p.A. 11.3.5 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Deleting the compressor operating hours Operate as follows: 1. 2. Access to the; see paragraph 11.3.1 “Access to the procedure”. Press and release the key (1) to select “rCH”, repeatedly press and release the + key (2) to set “149” and then press and release the SET key (3). Operate as follows to exit the procedure: 3. Press and release the ESCAPE key or do not operate for 60 s.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 11.4 List of configuration parameters The following table illustrates the meaning of the configuration parameters.
EVCO S.p.A. P5 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 0 1 ---- 1 enabling the condenser probe 1 = yes backlight configuration P8 0 1 ---- 1 0 = low brightness 1 = high brightness Par. Min. Max.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Par. Min. Max.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 duration of pre-dripping (only if parameter d1 is set at 1; d16 0 99 min 0 the compressor and evaporator fan will be off during predripping and the defrosting output will remain activated) Par. Min. Max. Unit Default Temperature alarms (9) (10) cabinet temperature below which the minimum temperature alarm is activated (relative to the work set-point, i.e.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 A14 ---- ---- ---- ---- Par. Min. Max. Unit Default reserved Evaporator and condenser fan evaporator fan activity during pre-cooling, blast chilling and deep freezing (if the parameter is set at 3, there will be effect also during storage) 0 = off, with digital control signal, i.e. via digital output K3 1 = on, with digital control signal, i.e.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 condenser temperature above which the condenser fan is F11 0 99 °C/°F (1) 15 switched on (intended as “F11 + differential and on condition the compressor is switched off); see also parameter F12 (4) (12) F12 0 240 s 30 F15 0 240 s 15 F16 -99 99 °C/°F (1) 20 condenser fan switch-off delay from compressor switch-off (only if parameter P5 is set at 0) evaporator fan delay from door closure, i.e.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 effect caused by the activation of the high pressure input i5 0 1 ---- 0 = no effect 1 = the compressor and the evaporator fan will be off and the condenser fan will be on.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 u6 1 240 min 5 u7 -99 199 °C/°F (1) 40 u8 0 240 min 2 switching on UV light for sterilisation cycle duration needle probe heating end temperature (temperature detected by the needle probe); see also parameter u8 maximum duration of needle probe heating; see also parameter u7 0 = needle probe heating is disabled needle probe heating on opening of the door, i.e.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 baud rate Lb 0 3 ---- 2 0 = 2,400 baud 1 = 4,800 baud 2 = 9,600 baud 3 = 19,200 baud parity LP 0 Par. Min. 2 Max.
EVCO S.p.A. (8) Vcolor 818 | Installer manual ver. 1.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 12 USE OF THE USB PORT 12.1 Foreword Through the USB port it is possible to make the following operation (from and in a text document): - upload and download of the configuration parameters - upload and download of the programs - download of the information relative to the HACCP alarms.
EVCO S.p.A. 8. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 To the end of the upload remove the USB peripheral from the USB port. 12.3 Upload and download of the programs To make the download of the programs operate as follows: 1. Make sure the device is in the “stand-by” status. 2. Insert an USB peripheral in the USB serial port. 3.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 To make the upload of the programs operate as follows: 5. Make sure the device is in the “stand-by” status. 6. Insert an USB peripheral in the USB serial port; make sure the peripheral contains the text document by name “recepits.bin” (see point 3). 7.
EVCO S.p.A. 12.4 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Download of the information relative to the HACCP alarms To make the download of the information relative to the HACCP alarms operate as follows: 1. Make sure the device is in the “stand-by” status. 2. Insert an USB peripheral in the USB serial port. 3.
EVCO S.p.A. 3.6 4. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the ESCAPE key or do not operate for 60 s. To the end of the download remove the USB peripheral from the USB port. To delete the information relative to the HACCP alarms see paragraph 9.3 “Deleting the information relative to the HACCP alarms”.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 13 ALARMS 13.1 Alarms The following table illustrates the meaning of the alarm codes. Code Meaning Temperature-controlled blast chilling or deep freezing not concluded within maximum duration alarm (HACCP alarm). Solutions: tiM - check the value of parameters r5 and r6 and AA. Main consequences: - the device will memorise the alarm - the alarm output will be activated. Minimum temperature alarm.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Low pressure alarm. Solutions: LP - check the conditions of the low pressure input - check the value of the parameter i8. Main consequences: - the compressor and the evaporator fan will be off - the alarm output will be activated. Compressor circuit breaker protection alarm. Solutions: CtH - check the conditions of the compressor circuit breaker protection input - check the value of the parameter i10.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 14 ERRORS 14.1 Errors The following table illustrates the meaning of the error codes. Code Meaning Cabinet probe error. Solutions: - check the value of the parameter P0 - check the integrity of the probe - check the device-probe connection - check the temperature of the cabinet.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Needle probe error 1. Solutions: - the same as the cabinet probe error (“Pr1” code) but relative to the needle probe 1.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 15 ACCESSORIES 15.1 Phase cut speed regulator for single phase fans EVDFAN1 15.1.1 Introduction EVDFAN1 is a phase cut speed regulator for single phase fans. The regulator control signal is the PWM type, the same supplied by the controller analogue output. The maximum current allowed on the fan is 5 A. 15.1.2 Description The following drawing illustrates the aspect of the EVDFAN1.
EVCO S.p.A. 15.1.3 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Dimensions The following drawing illustrates the EVDFAN1 dimensions; these are expressed in mm (in). 15.1.4 Connection to the device Operate as follows: 1. Make sure that parameter F0 is set at 3. 2. Cut the device power supply off. 3. Cut the EVDFAN1 power supply off. 4. Connect the device PWM analogue output to the EVDFAN1 control signal input. 5. Connect the evaporator fan to the EVDFAN1 phase cut output. 6.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 The following table illustrates the meaning of the PM 100A X9S001 parts. Part Meaning 1 power supply 2 RS-485 type serial port 3 On/stand-by LED 4 slot for paper advancement 5 slot for manual paper advancement 6 On/stand-by key 7 key for opening front panel 15.2.3 Dimensions The following drawing illustrates the PM 100A X9S001 dimensions; these are expressed in mm (in).
EVCO S.p.A. 15.2.4 Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Connection to the device Operate as follows: 1. Make sure that parameter L0 is set at 1. 2. Cut the device power supply off. 3. Disconnect the PM 100A X9S001 power supply. 4. Connect the device RD-485 serial port to the PM 100A X9S001 RS-485 type serial port. 5. Connect the device power supply. 6. Connect the PM 100A X9S001 power supply. For further information, consult the documentation relative to PM 100A X9S001.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 16 TECHNICAL DATA 16.1 Technical data Purpose of the device: operating control device. Construction of control: electronic control device to be incorporated. user interface control module self-extinguishing black. open frame. user interface control module 128.0 x 94.5 x 30.3 ± 0.4 mm 166.0 (5.039 x 3.720 x1.193 ± 0.015 (6.535 x 4.566 x 1.732 in; in; L x H x P). L x H x D).
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 user interface Power supply: supplied from control module the module. Rated impulse voltage: 4 KV. Overvoltage category: II. Software class and structure: A. control 115… 230 VAC (±15%), 50/60 Hz (±3 Hz), 10 VA max. incorporated (SuperCap). Battery autonomy in the event of a power-cut: 24 h with battery Clock: fully charged. Battery charging time: 2 min (the battery is charged by the device power supply).
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 8 outputs (electromechanical relays): - 1 x 16 A res. output @ 250 VAC SPST type (K1) for compressor management - 6 x 8 A res. outputs @ 250 VAC of which five SPST type for managing defrosting (K2), the evaporator fan (K3), the Digital outputs: condenser fan (K4), cabinet light or UV light (K7), the pump down valve or alarm output (K8) and one SPDT type for management of the door heating elements (K5) - 1 x 16 A res.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Vcolor 818 Controller for “top-class” blast chillers, with colour touch-screen TFT graphic display, in split version and which can be integrated into the unit Installer manual ver. 1.1 EB – 12/14 Codice 144VC818E114 This document is exclusive property of EVCO. Reproduction and disclosure are prohibited without express authorisation from EVCO.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 EVCO S.p.A. Via Feltre 81, 32036 Sedico Belluno ITALIA Tel. 0437 / 8422 Fax 0437 / 83648 info@evco.it www.evco.