EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO c-pro 3 micro SAVE c-pro 3 kilo SAVE PROGRAMMABLE CONTROLLER FOR AIR HANDLING UNITS WITH CROSS FLOW HEAT RECOVERY EXCHANGER ENGLISH APPLICATION MANUAL ver. 1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO Important Important Read this document thoroughly before installation and before use of the device and follow all recommendations; keep this document with the device for future consultation. The following symbols support reading of the document: indicates a suggestion indicates a warning.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO Index 1. GENERALITIES ........................................................................................................................................5 1.1 2. DIMENSIONS AND INSTALLATION .............................................................................................................6 2.1 Dimensions .............................................................................
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 6.7.2 Recovery heat exchanger anti-freeze protection ........................................................................... 47 6.7.3 Cross flow recovery heat exchanger and by-pass damper .............................................................. 49 6.8 Features of the COMPLETE control solution....................................................................................... 50 6.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 1. GENERALITIES 1.1 Description The application is dedicated to the control and regulation of the Air Handling Units with cross flow recovery heat exchanger. There are two solutions available: • COMPACT Control: Responds to minimum requirements and the Standards. • COMPLETE Control: Integrates the heating and high recovery efficiency functions to the Base solution.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 2. DIMENSIONS AND INSTALLATION 2.1 Dimensions 2.1.1 Dimensions of the control module c-pro 3 micro SAVE 4 DIN modules; dimensions are in mm (in). Terminal blocks molex-fit. 2.1.2 Dimensions of the control module c-pro 3 kilo SAVE 4 DIN modules; dimensions are in mm (in).
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 2.1.3 Dimensions of the Vgraph user interface The dimensions are expressed in mm (in). Dimension Minimum Typical Maximum A 104.0 (4.094) 104.0 (4.094) 104.8 (4.125) B 70.0 (2.755) 70.0 (2.755) 70.8 (2.787) C 22.0 (0.866) 23.0 (0.905) 24.0 (0.944) D 40.8 (1.606) 41.8 (1.645) 42.8 (1.685) 2.2 Installation 2.2.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO To remove the devices, first remove any terminal board with extractable screws inserted in the lower part and then operate on the DIN guide clip using a screwdriver, as indicated in the following drawing. 3 4 2.2.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 3. Applications 3.1 COMPACT Solution (make sure parameter PG00 has value 1; that is factory setting) The picture above shows a principle layout. It is intended for indicating the presence of the components, not their position, in the AHU controlled by the EVCO device. It is also NOT intended for indicating the real layout of the AHU.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO Electric connections with 3-speed fans Note: These connections are also valid for the version, only changes the type of terminal and the supply voltage.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 3.1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO RTC system clock - Real Time Clock. For driving the 3-speed fans (Digital output) set PG10=DO Electric connections with 1 speed fans + variator Note: These connections are also valid for the version, only changes the type of terminal and the supply voltage.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 3.2 COMPLETE Solution (make sure parameter PG00 has value 2) The picture above shows a principle layout, it is intended for indicating the presence of the components, not their position, in the unity controlled by the EVCO device.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO Electric connections with 3-speed fans Note: These connections are also valid for the version, only changes the type of terminal and the supply voltage.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 3.2.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO RTC system clock - Real Time Clock.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO Electric connections with 1 speed fans + variator Note: These connections are also valid for the version, only changes the type of terminal and the supply voltage.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 4. User interface 4.1 Display and keyboard Both control solutions (compact and complete) use the Vgraph user terminal equipped with LCD graphic display 128x64 pixel and 6 keys. The terminal can be panel mounted (IP 65 with optional gasket) on the unit or remote using EVCO wall box or in wall recess boxes type “506”.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 4.2 List of pages This paragraph presents the main pages and menus present in the application. The general menu is divided into three levels: user, installer and manufacturer, there is also a menu for the management of the system clock and some free access state pages.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO Every level password can be modified from the same level or higher levels. For instance any password can be modified from the manufacturer level. The range of values accepted for the passwords is: -999 / 9999. If no action is taken on a menu after 4 minutes the password inserted expires and it must be entered again. 4.2.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO In the VARIOUS PARAMETERS menu stand other general parameters, moreover, entering this menu it is possible to access the page for resetting the parameters to factory default values. In this menu you can change the user interface language (PH32). 4.2.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO In the VARIOUS PARAMETERS menu stand other general parameters, moreover, entering this menu it is possible to access the page for resetting the parameters to factory default values. 4.2.7 Main OFF page The main OFF page changes depending on the reason why the unit is OFF. There are three possibilities: 1. Unit OFF: Unit switched-off pushing the relevant key 2.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 4.2.8 Main ON page The main page is displayed when the unit is in ON mode: COMPACT VERSION Fans speed Recovery Heat Exchanger Bypass Information regarding the fans working mode: - COMFORT: Comfort period automatic Alarm icon: appears when there are active alarms. If all of them have becomes fixed, been viewed otherwise the (some icon active control - COMFORT+P.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO From the main page it is possible to access the state pages by pressing the RIGHT key. Pressing ESC it’s possible to go to the page for displaying the alarms and log. 4.2.9 State Pages From the main page it is possible to scroll the free access pages, which show the states of the controlled devices. These pages are not protected by password and can only be accessed with unit ON.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO Ok: correct reading State of the log Empty: empty memory Overflow: memory full Running number of the Alarm code Alarm value Date and time of In this page stand the information regarding the last element in the log. To view the previous element move the cursor on “Next>>” and push the ENTER key.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 5. Configuration parameters Below are listed all parameters managed by the application. A brief description, the range of acceptable values, unit of measurement, the default value proposed and the menu in which it is found is supplied for every parameter.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO PF30 PF31 PF32 Minima velocità per la regolazione modulante dei ventilatori Massima velocità per la regolazione modulante dei ventilatori Setpoint rampa di regolazione pressione statica 0.0 0.0 PF31 % IS-F 100.0 PF30 100.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO Wait for the NO (0) PH99 Reset the factory parameters default NO (0) NO (0) YES (1) - IS-D value to be read again on reset completion PSd2 Level 3 Installer level password (2) 0 -999 9999 - IS MANUFACTURER MENU CONFIGURATION PARAMETERS After modification of these parameters it is recommended to remove and then re-apply the power supply to the board.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO Differential for the by-pass of the recovery PF10 unit damper in anti-freeze protection 20.0 °C 36.0 °F 0 999 Sec CO-F 45 0 999 Sec CO-SE 15 0 999 Sec CO-SE 60 0 999 Sec CO-SE No (0) No (0) Yes (1) CO-SE 0 0 4 CO-SE 20.0 0.0 PS09 % CO-SE 100.0 PS08 100.0 % CO-SE 50.0 0.0 100.0 % CO-SE 2.0 0.0 20.0 °C CO-SE 4.0 0.0 20.0 °C CO-SE 2 0 2 2.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 3: 0-10V PH51 Logic of the digital input DI1 N.O. (0) N.O. (0) N.C. (1) - CO-V PH52 Logic of the digital input DI2 N.O. (0) N.O. (0) N.C. (1) - CO-V PH53 Logic of the digital input DI3 N.C. (1) N.O. (0) N.C. (1) - CO-V PH54 Logic of the digital input DI4 N.C. (1) N.O. (0) N.C. (1) - CO-V PH56 Logic of the digital input DI5 N.C. (1) N.O. (0) N.C.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO PT17 Saturday Working Working Not Working 0 0 1 Working Working Not Working 8000 0 100000 Hours IS-MA OR MAINTENANCE Functioning hours maximum limit for fans.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO PF22 Speed variator value corresponding to speed V2 66.50 0.00 100.00 % IS-F PF23 Speed variator value corresponding to speed V3 100.00 0.00 100.00 % IS-F PF30 Minimum speed for modulating fan 0.0 0.0 PF31 % IS-F PF31 Maximum speed for modulating fan 100.0 PF30 100.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO PSd1 User level password (1) 0 -999 9999 - CO-G PSd2 Installer level password (2) 0 -999 9999 - CO-G PSd3 Manufacturer level password (3) 0 -999 9999 - CO-G 3 0 999 2.0 PH01 PH02 0.0 20.0 °C 0.0 36.0 °F 1 99 Min 0.0 20.0 °C 0.0 36.0 °F 0 999 Sec 0.0 20.0 °C 0.0 36.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO PS08 Minimum opening damper mixing room 20.0 0.0 PS09 % CO-SE PS09 Maximum opening damper mixing room 100.0 PS08 100.0 % CO-SE PS10 Fixed value of damper open 50.0 0.0 100.0 % CO-SE 2.0 0.0 20.0 4.0 0.0 20.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO PH80 CAN communication Baud Rate (20K, 50K, 125K, 500K) 1 1 4 - CO-V Notes: The outside air return probes activation parameters, respectively PH41 and PH43 are conditioned by the state of PG01. If the input confirms the presence of the By-Pass, the two parameters are active, otherwise they are deactivated.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 6. REGULATIONS 6.1 State of the unit There are several unit switch-on/off procedures: 1) Via the relevant ON/OFF key Switch-ON: press the relevant key for about 2 seconds, if all the conditions are fulfilled the unit starts working (“ON” mode). Switch-OFF: press the relevant key for about 2 seconds, the unit stops working (“OFF” mode).
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 6.1.1 OFF state for alarm When the machine is active and an heavy alarm occurs the unit switches into the OFF due to alarm status. In this case the unit and all devices are switched OFF and the dampers are completely closed until the alarm condition has been reset.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 6.4 Restore the (factory) default parameters Via the “Parameters Reset” procedure it is possible to bring back the system parameters to the default value. The procedure can only be activated with machine in OFF mode Enter the Installer ->Various Parameters -> Default menu and press the ENTER key. Set the PH99 parameter to “YES”(1) and wait until it becomes “NO”(0) again on the display.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 6.6 Programming key It is possible to save the value of all system parameters into the programming key or upload them from the programming key. By means of this key is therefore possible also to copy the parameters from one device into one or more compatible ones. The saving or uploading operation can be carried out only with machine OFF, by connecting the key.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 6.7 Functionality of the COMPACT control solution This control solution offers the base functionality present also in the "complete" solution. 6.7.1 Supply and return fans The program manages two fans, supply and return. For the two fans is expected to ON / OFF control with three steps or analog output. .
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 6.7.1.3 Automatic regulation with presence sensor In addition to the previous regulation rules it is possible to modify the working Speed/capacity on the basis of a presence sensor. If the presence sensor is active (indicating there is someone inside the room), during the COMFORT time band the fans Speed/capacity is forced to the value set on parameter PF12. 6.7.1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 6.7.2.1 Unit without By-pass damper In this case the action taken for anti-freeze purpose is decreasing the fan speeds with a neutral zone control. Neutral Fan speed decrease Normal Working Zone every Tg Tg + T. Antifreeze When T ≤ Tg, the outlet fan speed will decrease progressively (V3-V2-V1) until stopping (V0).
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO PG03=1 The damper is managed with an analogue control via the analogue output AO3. When 0% the damper is closed, while when 100% the damper is open and the recovery heat exchanger is by-passed. 6.7.3 Cross flow recovery heat exchanger and by-pass damper The recovery heat exchanger to be used is the cross flow static type.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO After the (parameter Pr03) delay the by-pass damper is activated to allow defrosting. As soon as the exhaust air temperature is back above the accepted value the damper is deactivated and the recovery heat exchanger starts again. Note: If the anti-freeze probe is in alarm condition the function is disabled. 6.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 6.8.3 Fresh air intake damper It is possible to manage an optional motorised damper (can be enabled by parameter PG04=1) for fresh air intake purpose. The damper is managed via ON/OFF (digital) activation. The damper can be either fully open or fully closed, modulation is not possible as well as a minimum opening.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO Set Heating Point 100 % Free-heating 0% Pb02 / 2 Temperature Pb02 Note: If one of the probes is involved in the regulation error in the adjustment of the free-heating is no longer usable and the ramp of the heating rule on the total of the control differential.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO In case the control probe has an alarm condition it is possible to decide the opening percentage of the coil valve during alarm setting the Pb04 parameter. If Pb04 = 0.0% in probe error condition the valve remains closed. Anti-freeze safety on hot water circuit (AL04) The anti-freeze mechanical thermostat (digital input DI6) is mounted downstream the coil either inside or outside the pipe.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO In case the control probe has an alarm condition it is possible to decide the number of heaters to be activated during the the alarm by setting the Pb06 parameter. If Pb06=0 in probe error condition no heater is active. Heaters thermal overload alarm Via the DI6 (Electric heaters thermal overload protection) digital input it is possible to activate the heaters thermal overload alarm.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 6.8.7 Modulation of the air flow with CO2 probe This function is enabled only at the times COMFORT. It provides for the modulation of fan speed according to the value read by the probe of CO2 and is activated by setting PF01 = 3. The speed modulation takes place according to a PI control (if PF17 = 0 only proportional control).
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 7.1 Manual and automatic reset alarms As shown previously there are two types of alarm. Those with manual reset and those with automatic reset. For some alarms it is possible to set (Alarms Reset) the most suitable type of reset for user needs by means of the relevant parameters. Other alarms have predetermined reset type. 7.1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO - Alarm mnemonic code (AL01, AL03, …) - Alarm occurrence date and time - A possible value associated to the alarm The alarm mnemonic code is the one shown in the alarms table. The log can hold 100 events. Via the PH18 (Delete alarms log) parameter it is possible to cancel all the alarms stored in the log.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 8. MODBUS VARIABLES The controller can be managed by a supervisor via Modbus protocol. The communication takes place via optional TTL/RS485 serial interface outside the controller. The various states/parameters exported from the controller are shown below. 8.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 0x0608 1545 PT01_Start_Confort_TB ( Low ) 08:00:00 00:00:00 23:59:59 R/W 0x0609 1546 PT01_Start_Confort_TB ( High ) 0x060A 1547 PT02_Start_Economy_TB ( Low ) 20:00:00 00:00:00 23:59:59 R/W 0x060B 1548 PT02_Start_Economy_TB ( High ) 0x060C 1549 PT11a17_TypeDay[0] 0 0 1 0=Sunday,.. 6=Saturday R/W 0x060D 1550 PT11a17_TypeDay[1] 0 0 1 0=Sunday,..
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 0x0627 1576 PF08_DiffAntiFreeze 2.0 0.0 20.0 0x0628 1577 0x0629 PF09_DeadZoneOutsideTime 5 1 99 1578 PF10_DiffByPassAntiFreeze 2.0 0.0 20.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 0x064B 1612 PA12_EnableThermalResistor 1 0 1 R/W 0x064C 1613 PA13_ThermalResistorAlarm_Rele 1 0 1 R/W 0x064D 1614 PA15_FineCorsaAlarm_Rele 1 0 1 R/W 0x064E 1615 PA16_enHighTempAlarm 1 0 1 R/W 0x064F 1616 PA17_SetPointHT 85.0 -20.0 230.0 R/W 0x0650 1617 PA19_Diff_TempAlarm 3.0 0.0 36.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO 0x0691 1682 PF17_Ti 0 0 300 0x0692 1683 0x0693 PF30_MinSpeedFan 0.00 0.00 100.00 PF03 - Min speed fan R/W 1684 PF31_MaxSpeedFan 100.00 0.00 100.
EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104 EVCO c-pro 3 micro SAVE/ c-pro 3 kilo SAVE Application manual ver. 1.0 EB - 36/13 Code 144CP3UKSAE104 This document is exclusive property of EVCO. Reproduction and disclosure are prohibited without express authorisation from EVCO. EVCO is not liable for any features, technical data and possible errors stated in this document or deriving from use of the same.
EVCO S.p.A. c-pro 3 hecto SAVE | Application Manual ver. 1.0 | Code 144CP£SAE104 EVCO S.p.A. Via Feltre 81, 32036 Sedico Belluno ITALIA Tel. 0437 / 84.22 Fax 0437 / 83.648 info@evco.it www.evco.