EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Code 114CP3E324 c-pro 3 PROGRAMMABLE CONTROLLERS ENGLISH HARDWARE MANUAL ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 Important Important Read this document carefully before the installation and before the use and follow all the additional information for the installation and for the electrical connection; keep this document close to the devices for future consultations. The following symbols support the reading of the document: it indicates a suggestion it indicates an additional information to be followed.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 Index 1. INTRODUCTION ......................................................................................................................................................................5 1.1. 2. Introduction...............................................................................................................................................................................5 DESCRIPTION .........................................
EVCO S.p.A. 7.3. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 Vtouch .................................................................................................................................................................................... 98 7.3.1. Introduction .................................................................................................................................................................. 98 7.3.2.
EVCO S.p.A. 1. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 INTRODUCTION 1.1. Introduction c-pro 3 is a family of programmable controllers. The family consists of: - programmable controllers (c-pro 3 hecto, c-pro 3 hecto+, c-pro 3 mega, c-pro 3 mega+ and c-pro 3 NODE mega) - I / O expansions (c-pro 3 EXP hecto and c-pro 3 EXP hecto+). c-pro 3 hecto is available in blind version and can be used for example with an user interface such as Vgraph, Vtouch or Vroom.
EVCO S.p.A. - c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 5 analog inputs configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V ratiometric / 0-10 V transducers - 7 optoisolated digital inputs at 24 VAC / DC - 3 analog outputs of which 1 non optoisolated PWM output and 2 non optoisolated outputs configurable via configuration parameter for 0-20 mA / 4-20 mA / 0-10 V signal - 8 digital outputs (electromechanical relays) of which three 5 res.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 c-pro 3 EXP hecto+ is available in blind version and can be used for example with a programmable controller such as c-pro 3 hecto, c-pro 3 hecto+, c-pro 3 mega or c-pro 3 NODE mega.
EVCO S.p.A. 2. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 DESCRIPTION 2.1. Description c-pro 3 hecto and c-pro 3 hecto+ The following drawing shows the aspect of c-pro 3 hecto and of c-pro 3 hecto+. The following table shows the meaning of the parts of the controller.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 2.2. Description c-pro 3 mega The following drawing shows the aspect of c-pro 3 mega. The following table shows the meaning of the parts of the controller.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 2.3. Description c-pro 3 mega+ The following drawing shows the aspect of c-pro 3 mega+. The following table shows the meaning of the parts of the controller.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 13 programming and debugging port 14 power supply 15 analog inputs 6...
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 2.4. Description c-pro 3 NODE mega The following drawing shows the aspect of c-pro 3 NODE mega. The following table shows the meaning of the parts of the controller.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 2.5. Description c-pro 3 EXP hecto and c-pro 3 EXP hecto+ The following drawing shows the aspect of c-pro 3 EXP hecto and of c-pro 3 EXP hecto+. The following table shows the meaning of the parts of the expansion.
EVCO S.p.A. 3. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 SIZE AND INSTALLATION 3.1. Size c-pro 3 hecto, c-pro 3 hecto+, c-pro 3 EXP hecto and c-pro 3 EXP hecto+ 4 DIN modules; size in mm (in). 3.2. Size c-pro 3 mega and c-pro 3 mega+ 10 DIN modules; size in mm (in).
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 3.3. Size c-pro 3 NODE mega 14 DIN modules; size in mm (in).
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 3.4. Installation On DIN rail 35.0 x 7.5 mm (1.377 x 0.295 in) or 35.0 x 15.0 mm (1.377 x 0.590 in). To install the devices operate as shown in the following drawing. 1 2 To remove the devices remove possible extractable screw terminal blocks plugged at the bottom first, then operate on the DIN rail clips with a screwdriver as shown in the following drawing. 3 4 To install the devices again press the DIN rail clips to the end first.
EVCO S.p.A. 4. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 ELECTRICAL CONNECTION 4.1. Electrical connection c-pro 3 hecto and c-pro 3 hecto+ 4.1.1. Meaning of the connectors of c-pro 3 hecto and of c-pro 3 hecto+ The following drawing shows the connectors of c-pro 3 hecto and of c-pro 3 hecto. The following tables show the meaning of the connectors. MODBUS RS-485 port with Modbus master / slave communication protocol (configurable via application software).
EVCO S.p.A. 8 c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 not connected The maximum length of the connecting cables of the RS-485 port is 1,000 m (3,280 ft); also look at the Modbus specifications and implementation guides manual (the document is available on the internet site www.modbus.org). Connect the RS-485 port using a twisted pair. The following table shows the function codes supported by the controller.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 polarize the network of the RS-485 port (560 Ω, 0.25 W); position micro-switches 2 and 3 on position ON to polarize the - network of the RS-485 port (the network must be polarized by an element of the network same). plug in the termination of the CAN port (120 Ω, 0.5 W); position micro-switch 4 on position ON to plug in the termination of the - CAN port (plug in the termination of the first and of the last element of the network).
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 NO2 normally open contact digital output 2 CO3 common digital output 3 NO3 normally open contact digital output 3 CO4/5 common digital outputs 4 and 5 NO4 normally open contact digital output 4 NO5 normally open contact digital output 5 Digital output 6 (electromechanical relay).
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 Digital output 6 (electromechanical relay). Terminal Meaning CO6 common digital output 6 NO6 normally open contact digital output 6 NC6 normally closed contact digital output 6 The maximum length of the connecting cables of the digital(6) non hecto only) Analog outputs. Terminal Meaning VDC power supply driving analog output 1 (24 VDC, 50 mA max.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 For the settings about the analog outputs look at chapter 6 “CONFIGURATION”. The analog output 1 is usable on condition that the controller is powered in alternate current and the phase powering the controller is the same powering the user driven by the output. The analog output 1 and the analog output 2 are not independent each other but they work in the same way. DIGITAL INPUTS Free of voltage digital inputs.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 POWER SUPPLY Power supply. Terminal Meaning V≅ power supply controller (24 VAC / 20... 40 VDC) V≅ power supply controller (24 VAC / 20... 40 VDC) The maximum length of the connecting cables of the power supply of the controller is 30 m (98 ft). Protect the power supply with a fuse rated 0.8A-T 250 V. If the controller is powered in direct current, one will not have to respect the polarity of the power supply voltage.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 4.1.2. Example of electrical connection of c-pro 3 hecto The following shows an example of electrical connection of c-pro 3 hecto. To reduce the reflections on the signal transmitted through the cables connecting the devices each other, plug in the termination of the CAN port of the first and of the last element of the network.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 4.2. Electrical connection c-pro 3 mega and c-pro 3 NODE mega 4.2.1. Meaning of the connectors of c-pro 3 mega and of c-pro 3 NODE mega The following drawing shows the connectors of c-pro 3 mega and of c-pro 3 NODE mega. The following tables show the meaning of the connectors. MODBUS1 RS-485 port with Modbus slave communication protocol. The following drawing shows the aspect of the RS-485 port.
EVCO S.p.A. 8 c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 not connected The maximum length of the connecting cables of the RS-485 port is 1,000 m (3,280 ft); also look at the Modbus specifications and implementation guides manual (the document is available on the internet site www.modbus.org). Connect the RS-485 port using a twisted pair. The following table shows the function codes supported by the controller.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 3 not connected 4 D0 = B = - (terminal 0 of the transceiver) 5 D1 = A = + (terminale 1 of the transceiver) 6 not connected 7 not connected 8 not connected The maximum length of the connecting cables of the RS-485 port is 1,000 m (3,280 ft); also look at the Modbus specifications and implementation guides manual (the document is available on the internet site www.modbus.org). Connect the RS-485 port using a twisted pair.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 MICRO-SWITCH Micro-switch to: plug in the terminations of the RS-485 ports (120 Ω, 0.25 W); position micro-switch 1 on position ON to plug in the termination - of the first RS-485 port and micro-switch 2 on position ON to plug in the termination of the second RS-485 port (plug in the termination of the first and of the last element of the network) polarize the network of the second RS-485 port (560 Ω, 0.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 For the settings about the CAN port look at chapter 6 “CONFIGURATION”. Power supply user interface. Terminal Meaning GND ground VDC power supply user interface (24 VDC, 120 mA max.) The maximum length of the connecting cables of the power supply of the user interface is 30 m (98 ft). The controller incorporates a restorable thermal protection of the power supplies against the short circuit and the overload.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 NO8 normally open contact digital output 8 NC8 normally closed contact digital output 8 The maximum length of the connecting cables of the digital outputs is 100 m (328 ft). The maximum current allowed on the loads is 10 A. BMS CONNECTIVITY SLOT (in c-pro 3 NODE mega only) Slot for gateway c-pro 3 plug-in; also look at the User guide of c-pro 3 plug-in. ANALOG OUTPUTS Analog outputs.
EVCO S.p.A. DI7 c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 digital input 7 COM common digital inputs The maximum length of the connecting cables of the digital inputs is 100 m (328 ft). The digital inputs can be used on condition that they are powered at 24 VAC / DC. ANALOG INPUTS Analog inputs. Each analog input is configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V ratiometric / 0-10 V transducers.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 The maximum length of the connecting cables of the power supply of the controller is 30 m (98 ft). Protect the power supply with a fuse rated 2.5A-T 250 V. If the controller is powered in direct current, one will not have to respect the polarity of the power supply voltage.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 4.2.2. Example of electrical connection of c-pro 3 mega The following drawing shows an example of electrical connection of c-pro 3 mega. To reduce the reflections on the signal transmitted through the cables connecting the devices each other, plug in the termination of the CAN port of the first and of the last element of the network.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 4.3. Electrical connection c-pro 3 mega+ 4.3.1. Meaning of the connectors of c-pro 3 mega+ The following drawing shows the connectors of c-pro 3 mega+. The following tables show the meaning of the connectors. MODBUS1 RS-485 port with Modbus slave communication protocol. The following drawing shows the aspect of the RS-485 port. The following table shows the meaning of the pins of the RS-485 port.
EVCO S.p.A. 8 c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 not connected The maximum length of the connecting cables of the RS-485 port is 1,000 m (3,280 ft); also look at the Modbus specifications and implementation guides manual (the document is available on the internet site www.modbus.org). Connect the RS-485 port using a twisted pair. The following table shows the function codes supported by the controller.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 3 not connected 4 D0 = B = - (terminal 0 of the transceiver) 5 D1 = A = + (terminale 1 of the transceiver) 6 not connected 7 not connected 8 not connected The maximum length of the connecting cables of the RS-485 port is 1,000 m (3,280 ft); also look at the Modbus specifications and implementation guides manual (the document is available on the internet site www.modbus.org). Connect the RS-485 port using a twisted pair.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 MICRO-SWITCH Micro-switch to: - plug in the terminations of the RS-485 ports (120 Ω, 0.25 W); position micro-switch 1 on position ON to plug in the termination of the first RS-485 port and micro-switch 2 on position ON to plug in the termination of the second RS-485 port (plug in the termination of the first and of the last element of the network) - polarize the network of the second RS-485 port (560 Ω, 0.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 For the settings about the CAN port look at chapter 6 “CONFIGURATION”. Power supply user interface. Terminal Meaning GND ground VDC power supply user interface (24 VDC, 120 mA max.) The maximum length of the connecting cables of the power supply of the user interface is 30 m (98 ft). The controller incorporates a restorable thermal protection of the power supplies against the short circuit and the overload.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 NO8 normally open contact digital output 8 NC8 normally closed contact digital output 8 The maximum length of the connecting cables of the digital outputs is 100 m (328 ft). The maximum current allowed on the loads is 10 A. ANALOG OUTPUTS Analog outputs 1, 2 and 3. Terminal Meaning VDC power supply driving analog output 1 (24 VDC, 50 mA max.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 The maximum length of the connecting cables of the digital inputs is 100 m (328 ft). The digital inputs can be used on condition that they are powered at 24 VAC / DC. ANALOG INPUTS Analog inputs 1, 2, 3, 4 and 5.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 DIGITAL OUTPUTS Digital outputs 9 and 10 (electromechanical relays). Terminal Meaning NO10 normally open contact digital output 10 COM common digital outputs 9 and 10 NO9 normally open contact digital output 9 The maximum length of the connecting cables of the digital outputs is 10 m (32 ft). The maximum current allowed on the loads is 10 A. ANALOG OUTPUTS Analog outputs 4 and 5.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 For example: a CAN network can be made of a programmable controller, of four I / O expansions and of four user interfaces with baud rate 500,000 baud.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 ANALOG INPUTS Analog inputs 6, 7 and 8. Each analog input is configurable via configuration parameter for NTC / 0-20 mA / 4-20 mA transducers. Terminal GND Meaning ground AI6 analog input 6 AI7 analog input 7 AI8 analog input 8 +24V power supply 0-20 mA / 4-20 mA transducers (24 VDC, 120 mA max.) The maximum length of the connecting cables of the analog inputs and the one of the power supply of the transducers is 10 m (32 ft).
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 4.3.2. Example of electrical connection of c-pro 3 mega+ The following drawing shows an example of electrical connection of c-pro 3 mega+. It continues in the following page.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 To reduce the reflections on the signal transmitted through the cables connecting the devices each other, plug in the termination of the CAN port of the first and of the last element of the network.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 4.4. Electrical connection c-pro 3 EXP hecto and c-pro 3 EXP hecto+ 4.4.1. Meaning of the connectors of c-pro 3 EXP hecto and of c-pro 3 EXP hecto+ The following drawing shows the connectors of c-pro 3 EXP hecto and of c-pro 3 EXP hecto+. The following tables show the meaning of the connectors. MICRO-SWITCH Micro switch to plug in the termination of the CAN port (120 Ω, 0.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 The maximum length of the connecting cables of the CAN port depends on the baud rate of the CANbus communication, as follows: - 1,000 m (3,280 ft) with baud rate 20,000 baud - 500 m (1,640 ft) with baud rate 50,000 baud - 250 m (820 ft) with baud rate 125,000 baud - 50 m (164 ft) with baud rate 500,000 baud. Connect the CAN port using a twisted pair. For the settings about the CAN port look at chapter 6 “CONFIGURATION”.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 DIGITAL OUTPUTS In c-pro 3 EXP hecto+. Digital outputs 1, 2, 3, 4 and 5 (electromechanical relays).
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 The maximum length of the connecting cables of the PWM analog output is 1 m (3.280 ft); the one of the connecting cables of the 0-20 mA / 4-20 mA / 0-10 V analog outputs is instead of 30 m (98 ft). For the settings about the analog outputs look at chapter 6 “CONFIGURATION”.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 ANALOG INPUTS Analog inputs. Each analog input is configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V ratiometric / 0-10 V transducers. Terminal Meaning AI1 analog input 1 AI2 analog input 2 AI3 analog input 3 GND ground +5V power supply 0-5 V ratiometric transducers (5 VDC, 40 mA max.) +24V power supply 0-20 mA / 4-20 mA / 0-10 V transducers (24 VDC, 120 mA max.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 4.4.2. Example of electrical connection of c-pro 3 EXP hecto The following drawing shows an example of electrical connection of c-pro 3 EXP hecto. To reduce the reflections on the signal transmitted through the cables connecting the devices each other, plug in the termination of the CAN port of the first and of the last element of the network.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 4.5.
EVCO S.p.A. 5. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 USER INTERFACE 5.1. Keyboard The following table shows the meaning of the keyboard.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. 6. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 CONFIGURATION 6.1. Configuring a programmable controller 6.1.1. Configuring a built-in programmable controller To gain access to the procedure operate as follows: 1. Make sure the power supply is switched on. 2. Keep pressed 2 s buttons UP and DOWN: the display will show the following menu (hereinafter called Main menu). Info English Parameters ...
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 To modify the real date and time operate as follows: 19. From step 2, press and release button UP or button DOWN to select the voice Data e ora reale. 20. Press and release button ENTER. 21. Press and release button UP or button DOWN to modify the value. 22. Press and release button ENTER or button RIGHT to confirm the value and modify the following field (press and release button LEFT or button RIGHT to move among the fields). 23.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 6.1.2. Configuring a blind programmable controller The following procedures show an example of configuration of a blind programmable controller through a built-in programmable controller (in the example it is c-pro 3 mega) and through its user interface. It is also possible to configure the controller using an user interface; look at paragraph 6.3 “Configuring a device through an user interface”. Operate as follows: 1.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 6.2. Configuring an I / O expansion The following procedures show an example of configuration of an I / O expansion through a built-in programmable controller (in the example it is c-pro 3 mega) and through its user interface. It is also possible to configure the expansion using an user interface; look at paragraph 6.3 “Configuring a device through an user interface”. Operate as follows: 1.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 6.3. Configuring a device through an user interface (Vgraph, Vtouch or Vroom) The following procedures show an example of configuration of a device through an user interface (in the example Vgraph) and through its user interface. For further information please consult the hardware manual of the user interface. Operate as follows: 1. Switch off the power supply of the device and of the interface. 2.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 6.4. List of configuration parameters 6.4.1. List of configuration parameters of c-pro 3 hecto and of c-pro 3 hecto+ Submenu Parameter Min. Max.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 6.4.2. List of configuration parameters of c-pro 3 mega and of c-pro 3 NODE mega Submenu Parameter Min. Max.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 result of the copy of the parameters from the controller to the programming key EVKEY10 Diagnostic Key Par parameter available in read only modality and vice versa ok = operation successful err = operazione failed completed main cycle time of the application software Main time parameter available in read only modality Int.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 6.4.3. List of configuration parameters of c-pro 3 mega+ Submenu Parameter Min. Max.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 enabling the access to the first level page pressing a combination of buttons YES = yes, operating as follows: - keep pressed 3 s button ENTER to gain access to Parameters (2) [ press button RIGHT to the first page of level 1 En.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. Networks / CAN Bus Networks / CAN Bus c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. Networks / CAN2 Bus (4) Networks / CAN2 Bus (4) c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. Networks / MP Bus (5) Networks / MP Bus (5) Networks / MP Bus (5) Networks / MP Bus (5) Networks / MP Bus (5) c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. Networks / MP Bus (5) Networks / MP Bus (5) c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. 6.4.4. List c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 of configuration parameters of c-pro 3 EXP hecto and of c-pro 3 EXP hecto+ Submenu Parameter Min. Max.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. 7. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 USER INTERFACES 7.1. Preliminary information The controllers in blind version can be used for example with an user interface such as Vgraph, Vtouch or Vroom. 7.2. Vgraph 7.2.1. Introduction Vgraph is a new and innovative user interface for the programmable controllers of the family c-pro 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 7.2.3. Size Size in mm (in). Size Minimum Typical Maximum A 104.0 (4.094) 104.0 (4.094) 104.8 (4.125) B 70.0 (2.755) 70.0 (2.755) 70.8 (2.787) C 22.0 (0.866) 23.0 (0.905) 24.0 (0.944) D 40.8 (1.606) 41.8 (1.645) 42.8 (1.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 7.3. Vtouch 7.3.1. Introduction Vtouch is a new and innovative user interface for the programmable controllers of the family c-pro 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 7.3.3. Size Size is in mm (in). Size Minimum Typical Maximum A 104.0 (4.094) 104.0 (4.094) 104.8 (4.125) B 70.0 (2.755) 70.0 (2.755) 70.8 (2.787) C 22.0 (0.866) 23.0 (0.905) 24.0 (0.944) D 40.8 (1.606) 41.8 (1.645) 42.8 (1.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 7.4. Vroom 7.4.1. Introduction Vroom is a new and innovative user interface for the programmable controllers of the family c-pro 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 7.4.3. Size Size in mm (in). Size Minimum Typical Maximum A 104.0 (4.094) 104.0 (4.094) 104.8 (4.125) B 70.0 (2.755) 70.0 (2.755) 70.8 (2.787) C 22.0 (0.866) 23.0 (0.905) 24.0 (0.944) D 40.8 (1.606) 41.8 (1.645) 42.8 (1.
EVCO S.p.A. 8. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 ACCESSORIES 8.1. Programming kit EVIF20TUXI 8.1.1. Introduction EVIF20TUXI is a programming kit. Through the kit it is possible to program the controllers with the application software realized through UNI-PRO 3. The kit is made of: - TTL / USB isolated serial interface - USB cable (to connect the serial interface to the Personal Computer) - TTL cable (to connect the serial interface to the controller). 8.1.2.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 8.1.3. Size Size is in mm (in). 8.1.4. Connection to the Personal Computer Operate as follows: 1. Plug in an end of the TTL cable into the TTL port of the serial interface. 2. Plug in the other end of the TTL cable into the programming and debugging port of the controller. 3. Plug in and end of the USB cable into the USB port of the serial interface. 4.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 The following table shows the meaning of the parts of the key. Part Meaning 1 telephone connector 2 connector for power supplier EVPS 8.2.3. Size Size is in mm (in). 8.2.4. Connection to the controller Operate as follows: 1. Plug in the telephone connector of the key into the programming and debugging port of the controller. To copy the parameters from the controller to the key and vice-versa look at chapter 6 “CONFIGURATION”.
EVCO S.p.A. 9. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 TECHNICAL DATA 9.1. Technical data Purpose of control: programmable controller for applications in refrigeration, ventilation and air conditioning. Construction of control: electronic control device to be incorporated. Box: self-extinguishing grey UL94 V0. Heat and fire resistance category: D. Size: c-pro 3 hecto and c-pro 3 c-pro 3 mega and c-pro 3 c-pro 3 EXP hecto and hecto+ mega+ c-pro 3 EXP hecto+ 179.0 x 128.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 The maximum lengths of the connecting cables are the followings: • power supply controller: 30 m (98 ft) • analog inputs: 100 m (328 ft), but AI6, AI7 and AI8 of c-pro 3 mega+ (10 m, 32 ft) • power supply transducers: 10 m (32 ft) • digital inputs: 100 m (328 ft), but DI8, DI9, DI10, DI11 and DI12 of c-pro 3 mega+ (10 m, 32 ft) • PWM analog output: 1 m (3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 Ambient conformity: ROHS 2002 / 95, WEEE 2002 / 96 / EC, REACH CE 1907 / 2006. EMC conformity: EN / IEC 60730-1 enclosure 16. 24 VAC (±15%), 50 / 60 Hz (±3 Hz), 30 VA max. isolated or 20... 40 VDC, 22 W max. isolated, supplied by a class 2 circuit. The devices incorporate a protection against the reversal of polarity.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 NTC analog inputs (10K Ω @ 25 °C, 77 °F) Kind of sensor: NTC 2. Working range: from -40 to 86 °C (-40 to 186 °F). Accuracy: ±1 °C. Resolution: 0.1 °C. Conversion time: 100 ms. Protection: no protection. NTC analog inputs (10K Ω @ 25 °C, 77 °F) Kind of sensor: NTC 2. Working range: from -40 to 86 °C (-40 to 186 °F). Accuracy: ±0.7% of the full scale between -40 and 100 °C, ±1 °C Resolution: 0.1 °C.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 5 optoisolated digital inputs 12 optoisolated digital inputs 5 optoisolated digital inputs at 24 VAC / DC. at 24 VAC / DC. at 24 VAC / DC. Non optoisolated free of voltage digital inputs Power supply: no power supply. Input resistance: ≥ to 10K Ω. Protection: no protection. Optoisolated digital inputs at 24 VAC / DC Displays: Power supply: 24 VAC (±15%), 50 / 60 Hz (±3 Hz) or 24 VDC (+66% -16%).
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 PWM analog outputs (but the analog outputs 4 and 5 of c-pro 3 mega+) Driving power supply: 24 VDC (+16% -25%), 50 mA max. Frequency: the same as the one of the phase powering the device. Protection: no protection. 0-20 mA / 4-20 mA analog outputs 40... 300 Ω. Input resistance: Accuracy: ±3% of the full scale. Resolution: 0.05 mA. Conversion time: 1 s.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 10 outputs (electromechanical relays): 6 outputs (electromechanical • 250 VAC (6,000 relays): • cycles) five 3 res. A @ SPST outputs (K1, K2, • output (K6). • SPST outputs (K2, K3, K4 and K6) • one 8 res. A @ 250 VAC (6,000 cycles) five 3 res. A @ 250 VAC (6,000 cycles) four 8 res. A @ cycles) 250 VAC (6,000 SPDT relays): SPST outputs (K1, K2, 250 VAC (6,000 one 5 res.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 c-pro 3 PROGRAMMABLE CONTROLLERS Hardware manual ver. 3.2 PT - April 2013 Code 114CP3E324 This document belongs to EVCO; unless you are authorized by EVCO, you can not publish it. EVCO does not take any responsibility about features, technical data and possible mistakes related in this document or coming by its use. EVCO does not take any responsibility about damages coming by the non-observance of the additional information.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324 EVCO S.p.A. Via Feltre 81, 32036 Sedico Belluno ITALY Phone +39 / 0437 / 8422 Fax +39 / 0437 / 83.648 info@evco.it www.evco.