CONFIGURATION PARAMETERS AND DEFAULT VALUES SUMMARIZING TABLE
User Menu configuration parameters
LABEL MIN. MAX. U.M. DEF. CONDENSER FANS REGULATOR
F 0 0.001 255 (4) 2.00 proportional band (1)
F 1 F 6 F 7 (4) 12.00 condenser fans activation setpoint (1)
F 6 -999 9999 (4) 0.00 minimum condenser fans activation setpoint programmable (1)
F 7 -999 9999 (4) 30.00 maximum condenser fans activation setpoint programmable (1)
F A 0 1 ---- 0 condenser fans functioning
F d 0 1 ---- 0 method used to compute which condenser fans activate/deactivate
F H 0 9999 hour 9999 number of total working hours of the condenser fans enough to signal the request of service (1)
LABEL MIN. MAX. U.M. DEF. DIGITAL INPUTS
i1P 0 1 ---- 0 kind of contact of the user compressor associated to the output K1 ... 8 locking digital inputs
i2P 0 1 ---- 0 kind of contact of the user condenser fans associated to the output K1 ... 8 locking digital inputs
i4P 0 1 ---- 0 input configuration (freon level or by-pass regulation)
i5P 0 1 ---- 0 kind of contact of the input freon level/by-pass regulation
i6P 0 1 ---- 0 kind of contact of the condenser fans safety digital input
i7P 0 1 ---- 0 kind of contact of the upper condensing quantity digital input
i8P 0 1 ---- 0 kind of contact of the lower pressure digital input
LABEL MIN. MAX. U.M. DEF. LOWER PRESSURE ALARM
AA0 0.001 255 (3) 0.01 hysteresis (differential)
AA1 -999 9999 (3) 0.00 alarm setpoint
AA4 0 2 ---- 0 kind of alarm
AA7 0.00 4.15 min,sec0.00 disabling time to the lower pressure alarm activation
AAn 0 15 ---- 0 number of lower pressure alarms enough to give the instrument locking
LABEL MIN. MAX. U.M. DEF. UPPER PRESSURE ALARM
Ab0 0.001 255 (3) 0.01 hysteresis (differential)
Ab1 -999 9999 (3) 0.00 alarm setpoint
Ab4 0 2 ---- 0 kind of alarm
Ab7 0.00 4.15 min,sec0.00 disabling time to the upper pressure alarm activation
Abn 0 15 ---- 0 number of upper pressure alarms enough to give the instrument locking
LABEL MIN. MAX. U.M. DEF. UPPER CONDENSING QUANTITY ALARM
AC0 0.001 255 (3) 0.01 hysteresis (differential)
AC1 -999 9999 (3) 0.00 alarm setpoint
AC4 0 2 ---- 0 kind of alarm
AC7 0.00 4.15 min,sec0.00 disabling time to the upper condensing quantity alarm activation
ACn 0 15 ---- 0 number of upper condensing quantity alarms enough to give the instrument locking
LABEL MIN. MAX. U.M. DEF. PRESSURE ALARMS DISABLING
A 3 0.00 4.15 h,min 0.00 disabling time to the upper pressure alarm activation from the instrument start
A 6 0.00 4.15 h,min 0.00 time required to clear the pressure alarms counters
LABEL MIN. MAX. U.M. DEF. CONNECTION IN A SERIAL NETWORK WITH EVCOBUS PROTOCOL COMMUNICATION
L 1 1 15 ---- 1 instrument address
L 2 0 7 ---- 0 instrument group
L 4 0 3 ---- 1 baud rate
LABEL MIN. MAX. U.M. DEF. OPERATOR MENU PASSWORD VALUE