16
upper condensing quantity alarms counter as long as the number of
upper condensing quantity alarms enough to give the instrument lock-
ing gets reached (the increasing of the upper condensing quantity
alarms counter gets given also by the upper condensing quantity dig-
ital input activation; see the paragraph Digital inputs on the page 13);
to unlock the instrument turn off and turn on again the instrument.
The parameter AC4 establishes the kind of upper condensing quantity
alarm that the instrument must manage: the upper condensing quan-
tity alarm never gets activated, absolute upper condensing quantity
alarm (in this case the instrument activates the upper condensing quan-
tity alarm when the quantity read by the condensing probe rises above
the alarm setpoint) ...
... or upper condensing quantity alarm relative to the setpoint estab-
lished with the parameter F 1 (in this case the instrument activates the
upper condensing quantity alarm when the quantity read by the con-
densing probe rises above the condenser fans activation setpoint of the
alarm setpoint value).
Speaking of upper condensing quantity alarm
the parameter i7P establishes the kind of contact of the upper
condensing quantity digital input
the parameter AC0 establishes the hysteresis (differential) rela-
tive to the alarm setpoint
the parameter AC1 establishes the alarm setpoint value
the parameter AC4 establishes the kind of upper condensing
quantity alarm that the instrument must manage
the parameter AC7 establishes the time that disables an upper
condensing quantity alarm activation from the moment in which
the upper condensing quantity alarm happens
the parameter ACn establishes the number of upper condens-
ing quantity alarms enough to give the instrument locking
the parameter A 6 establishes the time that must pass from the
moment of a previous alarms counter increasing in order that
the counter get cleared
the parameters i7P, AC0, AC1, AC4, AC7, ACn and A 6 belong to the
User Menu; see the chapter User Menu on the page 32.
FUNCTIONING
Upper condensing quantity alarm