User Manual
26
EN
4. Pull the cable from the top of the unit. The power cable needs to be attached to the
terminal block located on the top of the unit. Strip the ends of the power supply cables,
if not done already.
5. Using a screw driver, push the spring clamps to connect the power supply cables to the
power line terminal blocks labeled L1, GND (ground) and L2. The ground (often green
or yellow/green) must be connected to GND, L1 (often brown or black) is connected to
terminal L1, and L2 (often white) is connected to terminal block L2.
Step 4: Wiring the station
Running the power cable:
• Lead the power supply cable into the bottom of the pole/bracket and through the wire
opening slot.
• Gently snake the wire through the pole/bracket and ensure that it protrudes at least
1.5 – 2 feet outside of the central wire exit.
• Ensure that the power supply cable has sufcient length inside the pole to prevent power
supply line damage by small movements of the pole or bracket.
4a. Wiring the BusinessLine Single (pole/wall/retractor)
1. Insert the power cable through the hole in the back plate.
2. Snake the power cable upwards into the tunnel above the hole.
3. Continue snaking the power cable from behind the components using the tunnel.