Installation guide
50
0 - The bell relay will reset after the bell time expires and will not retrigger on any further zone
violations.
1 - The bell relay will reset after the bell time expires and will retrigger when a zone is violated.
2 - The bell relay will reset after the bell time expires only if all zones on the system have closed
(restored). If any of the zones are open (in alarm), then the bell relay will remain operated.
BELL TIME 900: This is the time in seconds that TIMED BELL panel relay output 7 and
output C-LEM 7 will operate before an automatic shutdown.
L ENABLE DURESS ? 0: The old DURESS function has been changed. This variable is used to
activate the revised Duress alarm feature. Leave the variable at 0 to deny the Duress alarm
feature or change it to 1 to enable the Duress alarm feature. To create a duress alarm, the user
must enter a zero (0) and then their code and then press a valid function key (e.g., FULL
DISARM). It does not matter what the function is because it will be executed and a Duress alarm
sent as well.
L TX FULL ARM/DIS ? 0: As each area in the system is armed, a message will be sent to the
central/monitoring station indicating the arming of that area. When the last area in the system is
armed an additional message indicating that now the system is fully armed can also be sent to
the station. Similarly, when the first area of the system is disarmed, an additional message
indicating that the system is disarmed (because now the system is not fully armed) can be sent to
the station. This is of benefit to manual stations; however, it can cause problems with the
armed/disarmed closing routines in certain automation packages. If desired, change this variable
to a 1 to turn on the extra messages.
L COMMS TEST 0: This variable is used to cause a periodic communications test to be sent to
the central/monitoring station. Such a test can be used to prove the integrity of the system in low
traffic applications such as fire alarm panel monitoring, sprinkler riser monitoring, building
temperature monitoring, etc.. To select the frequency of the testing, you must enter a numeric
value (e.g., 0= No test, 1= Every day, 2= Every second day, 3= Every third day, etc.). The test
will occur at 03:00 hours (default time) and this time can be changed by using the SET TIME
COMMANDS function (see page 59).
L SUPVRY SHUTDOWN 0: This variable is used to allow a fixed number of alarm and restore
signals from a sprinkler riser (gate valve, post indicator valve, or pressure drop switches) to be
sent to the central/monitoring station, after which no more signals are sent for a period of 90
minutes (5400 seconds) or unless the service technician manually resets the timer either by
simply pressing the FULL DISARM key once or by entering his or her code and then pressing
the FULL DISARM key. This shutdown does not apply to the FIRENO or FLOW zones!.