Installation guide

49
EXIT-4 TIME 30: If an EXIT-4 zone type has been assigned, this variable sets the amount of
exit and entry delay time allowed for exit from and entry into area 4.
SHUNT LIMIT 99: This is the highest zone number that can be shunted. Important zones like
FIRENO, PANIC, or HOLDUP should be assigned high zone numbers and this value lowered to
prevent the accidental shunting (bypassing) of those zones.
ALERT & DISPLY? 1: This variable is used to enable the control panel and the remote keypad
displays to sound piezo-alert warnings on activation of a 24HOUR or FIRENO zone type. Enter
a 0 to turn off the piezo-sounder.
COMMON AREA ? 0: If the premises has a common area, such as a lobby, cafeteria, hallway,
etc., and protection of this area is desired, set this variable to 1.
FULL ARM DISPLAY 0: This variable controls the action of the display in the FULL ARM
mode. It can be set to one of the following values:
0 - The display remains blank.
1 - ALERT messages only are displayed.
2 - ALERT and WARNING messages are displayed.
3 - ALERT messages, WARNING messages, OPEN zones, and
DATE/TIME are displayed.
4 - OPEN zones display zone state plus description.
For example: If, while the panel is armed, an immediate display of an alarm is required, then set
the variable to 1.
LOG OUTPUTS ? 0: When a panel relay output or a output C-LEM is operated or reset, this
action can be stored in the panel log and simultaneously be printed on a printer. As this action
creates unnecessary, wasteful log data, it should only be used in certain instances. If needed, set
this variable to 1.
AUDIBLE TECH ? 0: This variable allows for an audible alert from a TECH zone. Change this
value to a 1 to cause the piezo-sounder to beep when an alarm occurs on a TECH zone.
RETARD TIME 3: This variable is used to set the amount of retard time that must expire
before a FLOW zone type will create an alarm. The allowable values are 1 second to 60 seconds.
Values entered outside this range will default to the minimum (3) or maximum (60) values.
PROGRAMMING THE PANEL cont.
RETRIGGER 1: This variable controls the retriggering of the external bell relay during an
alarm. It can be set to one of the following values: