PROGRAMMING THE PANEL cont
this mode. As the exit occurs, the panel beeps and then briefly displays the number of shunts in
place. To exit at any time, press the RETURN key or the NO key.
SERVICE MODE (A key): To select this mode, enter the Service user code and then press the
A key (shift YES). The display will show a flashing sub-menu: REPORT--TEST-MONITOR.
ON-LINE REPORT - The on-line report displays all zones that are connected to the panel and
whose state was not disconnected or shorted at the last LEM-line initialization. The report starts
with the lowest-numbered zone and increases numerically until all the on-line zones have been
reported. To select the on-line report, press the FULL DISARM key. In a polled [DVACS
(tm)
]
installation without a Model 3302R3 port splitter, the panel cannot print a report and will
immediately start displaying the report. In a non-polled installation (local printer) or a polled
installation with a Model 3302R3 port splitter, the display will show PRINT ON-L REPORT ?.
Press the YES key to make a hard-copy record of the on-line report. While the printing is in
progress, the display will show PRINTING ON-L REPORT. If a printed copy is not required,
press any other key. The on-line report will now be scrolled on the display. As in the SYSTEM
LOG function above, you may use the RETURN key and the AUDIBLE SILENCE 1 key to
advance or rewind the display. The NO key will abort the report. When the display shows
QUIT ?, you may chose to return to the sub-menu by pressing the NO key or exit this function
by pressing the YES key.
WALKTEST - This option, selected by pressing the AUDIBLE SILENCE 2 key, is designed to
ensure that all zones and their associated detectors are working correctly [i.e., reporting open
(alarm) and closed (restored) conditions]. If possible, connect a printer to the panel when
performing a walktest for a concise, date-stamped report showing the name and address of the
installation, the number of zones tested, and a list of any untested zones.
In this option, the panel will display WALKTEST for a moment, followed by TEST 1 (if zone 1
is on line!). To identify zone 1, press the HELP key and the display will briefly show the zone
description. When zone 1 is activated, the panel will report this by displaying TEST 2 : 1
CLOSED. It has now set up for zone 2 and is waiting until that zone is activated before
proceeding. (In the phrase TEST 2 : 1 CLOSED, 2 represents the zone on the system that is to
be tested and 1 represents the last zone operated.)
If zones other than the one requested by the display are activated, their number and state (open or
closed) will be shown; however, the panel will not ask for them when their position in the
sequence occurs. If a zone cannot be tested, it may be disregarded by pressing any key. The NO
key is used to exit.
TIMED BELL panel relay output 7 can be turned on very briefly (less than one second) on every
zone change by pressing the FULL ARM key. Pressing the FULL ARM key again will cancel
this function. This is useful to the serviceperson when working alone.