Owner`s manual

APPENDIX TWO
WIRING to a HOME AUTOMATION SWITCH (OPTIONAL)
External control of your H Series replace is an either/or proposition; you control it with either a home
automation switch (not included) or the remote control (included). The home automation system cannot
adjust the ame height; it can only turn on (with a high ame) or o.
When using a home automation system:
1. The jumper across X4 is removed and replaced with a DRY CONTACT CLOSURE (DCC, millivolt-rated, MUST
make clean break) using a Phoenix Contact GMSTB 2,5/ 2-ST-7,62 plug (not included.)
2. The remote control must then be disconnected from the system by pressing the SW1 button (see gure
above) TWICE in succession.
From then on, when the DCC is closed the re goes on to high ame and when the DCC is opened the re
goes o. The ame height cannot be adjusted with the home automation system.
IFC
Control
Module
Power Plug
Gas Valve
Pilot Burner
X4 X5
X1
SW1
Back-up
Battery
Case
DCC
Connects
Here
(see text)