Owner`s manual
H Series Vent Free Gas Fireplace EuropeanHome.com
TRIM and FINISH
19
A
B
Figure 11. NON-Combustible Facing Dimensions
HVF-42-3S, HVF-60-3S and HVF-72-3S WALL FACING
B
B
C
C
Figure 12. NON-Combustible Facing Dimensions (Left Side)
Figure 13. NON-Combustible Facing Dimensions (RightSide)
All of the following limits MUST be maintained for installations of the HVF-42-3S, HVF-60-3S and HVF-72-3S:
• The bottom of the cabinet may be no closer to the room ceiling than 36”.
• The minimum interior height of an enclosing chase is 34½”.
• Figures 11-13 show the combustible facing limit for the H Series Vent Free Gas Fireplaces listed in Table 5,
above. Combustible wall facing is NOT permitted inside this limit. Dimension “A” is measured up from the
top of the replace opening and the “B” and “C” dimensions are centered on the cabinet.
Table 5. NON-Conbustible Facing Dimensions
Dimension HVF-42-3S HVF-60-3S HVF-72-3S
A 47” 60” 72”
B 4” 4” 4”
C 18” 18” 18”