PRE-INSTALLATION PLANNING
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
When installing the H Series Fireplaces, the clearances shown in the table below must be observed. If the
required clearances are not maintained a re may result thereby causing property damage, personal injury
or loss of life.
When the replace is to be installed directly on carpeting, vinyl tile or combustible material other than wood
ooring, it must be installed on a metal or wood panel extending the full width and depth of the replace
cabinet.
When enclosing your replace, the use of non-combustible building materials
is required. Please read and understand the COMBUSTIBLE MATERIALS and
NON-COMBUSTIBLE MATERIALS sections on page 10.
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
HVF-42-3S
HVF-60-3S
HVF-72-3S
Clearance to Top Cabinet Standos 0.0”
Clearance to Side Cabinet Standos 0.0”
Clearance to Cabinet Rear 0.0”
Clearance to Wood Floor 0.0”
Distance Between Cabinet Bottom and Enclosure Ceiling 34½”
Distance Between the Opening and a Side Wall in Front of the Fireplace 6.0”
Table 3. Minimum Clearances to Combustible Materials