Page 2 2 INTRODUCTION/WARRANTY - WHAT IS A CONDENSING BOILER? AMBASSADOR (KITCHEN), COUNTRYMAN (OUTDOOR) & CONSUL (BOILERHOUSE) CONSENSING BOILERS USER INSTRUCTIONS - BOILER OPERATION - SWITCHING THE BOILER ON - BOILER CONTROLS - SWITCHING THE BOILER OFF / BURNER LOCKOUT / RESTARTING AFTER LOCKOUT - RESTART INSTALLATION - REGULATIONS / WATER CONNECTIONS - BOILER LOCATION - CONNECTING OIL SUPPLY - ELECTRICAL CONNECTION/WIRING DIAGRAM 3 3 3 4 5 6 7 8 9-10 11 TECHNICAL DATA - BOILER SPECIFICATIONS 12-14
INTRODUCTION Thank you for choosing our condensing oil boiler, please read the following carefully. To the installer This manual must be left with the householder by the installer who will instruct the user on the boiler operation.
USER INSTRUCTIONS Reset Button BOILER OPERATION The Boiler Control Thermostat responds to the temperature of the water within the boiler and switches power to the burner when heat is required. The burner has an independent control system which regulates the firing and (shut-off) of the burner.
BOILER CONTROLS BOILER CONTROL THERMOSTAT The temperature of the water within the boiler is controlled and maintained by the Boiler Control Thermostat located on the boiler control panel. TEMPERATURE SETTINGS: The Boiler Control Thermostat has a range of 50°C to 80°C.
SWITCHING THE BOILER OFF The boiler can be switched off at anytime using one of the following: - Turn the boiler control thermostat to the OFF position - Switch the mains (electrical supply) to OFF - Set the control system to OFF (e.g. Time Clock) PLEASE NOTE: For longer periods of shutdown e.g. while away on holiday, switch OFF the mains (electrical supply) and turn OFF the OIL supply. If shutdown occurs during cold weather ensure boiler is protected against frost damage.
RESTART - Check there is adequate oil in the storage tank. - Check oil supply valves are open - Switch on heating system (e.g. Time Clock) - Press the Burner Reset Button on the burner Control Box, which will be illuminated. The Burner Reset Button (illuminated)(Fig 1) will go out and the burner will commence the ignition start sequence. After 15 seconds the Burner should fire normally.
REGULATIONS The installation of oil-fired boilers should comply with the following standards and codes of practice: - BS5449 Forced circulation hot water heating systems for domestic use. - BS5410-Part 1 Oil installations up to 45kw - BS7593 Water treatment of hot water central heating systems - BS7671 Electrical Regulations - Building Regulations Part 1L and J 2002 England and Wales, Part F Scottish Regulations and Technical Booklet L Northern Ireland.
BOILER LOCATION Sound levels should be discussed with the householder, as some people may be sensitive to low noise levels in a small room, as is may appear more annoying than in larger rooms. Please Note installation should take into account of flue position (see diagram). RECOMMENDED FLUE POSITION Issue No.1 Combined Manual 24.10.
OIL SUPPLY Issue No.1 Combined Manual 24.10.
OIL SUPPLY A flexible oil pipe is supplied to connect the burner to the incoming oil supply pipe. IMPORTANT NOTES: - If sitting oil tank above burner height, use single supply pipe only. - If sitting oil tank below burner height, use twin pipe supply or Tiger loop. - Please refer to Burner Manual for conversion to oil pump for two pipe system. Issue No.1 Combined Manual 24.10.
ELECTRICAL ENTRY The electrical supply to the boiler must be wired using a double pole-isolating switch 230v/50hz, fused 5 amps. The mains supply must be connected with the boiler dual stat, the supply will then continue down to the burner control box. The burner is supplied with a three wire cable plug which allows disconnection for maintenance. Issue No.1 Combined Manual 24.10.
BOILER SPECIFICATIONS FOR AMBASSADOR (KITCHEN) DIMENSION A B C D E F G H I J K 15/21 Kw 854 589 421 140 560 706 35 355 293 423 741 21/27 Kw 854 589 481 140 528 706 35 355 293 423 741 27/38 Kw 854 589 481 140 528 706 35 355 293 423 741 35/50 Kw 995 657 581 115 628 889 35 370 293 491 889 DIMENSIONS ARE IN (mm.) Electrical Supply.
BOILER SPECIFICATION FOR COUNTRYMAN OUTDOOR DIMENSIONS A B C D E F 15/21 Kw 521 868 750 894 880 485 21/27 Kw 521 868 750 894 880 485 27/38 Kw 521 868 750 894 880 485 DIMENSIONS ARE IN (mm.) General Data Electrical Supply. 240w-50hz Fuel: 28 Second Oil Supply Connection ¼” BSP High Limit Stat: Manual Reset Maximum Control Thermostat Setting 85°C Maximum Operating Pressure: 3 Bar – 45psi – 28m Static head room 92ft Draught Limit Min 12.5 Nm2 – 0.05” WG Max 33.0 Nm2 – 0.
BOILER SPECIFICATION FOR CONSUL BOILERHOUSE DIMENSION A B C D E F G H 15/21 KW 436 402 568 385 559 694 138 352 21/27 KW 440 402 568 453 527 694 142 357 27/38 KW 440 402 568 453 527 694 142 357 DIMENSIONS ARE IN (mm.) General Data Electrical Supply. 240w-50hz Fuel: 28 Second Maximum Control Thermostat Setting 85°C Oil Supply Connection ¼” BSP High Limit Stat: Manual Reset Maximum Operating Pressure: 3 Bar – 45psi – 28m Static head room 92ft Draught Limit Min 12.5 Nm2 – 0.05” WG Max 33.0 Nm2 – 0.
SERVICING INSTRUCTIONS A competent service engineer OFTEC registered should be appointed on an annual basis. • Remove inspection door, burner and baffle assembly • Brush down the inside of the heat exchanger and vacuum out debris • Clean baffle assembly • Pull out inserts from stainless steel heat exchanger and clean before replacing. Ensure stainless steel heat exchanger is thoroughly cleaned. • Empty and clean condensing trap (Fig.
BAFFLE ASSEMBLY INSERT L/H STACK 2 SET OF BAFFLES 27/38 KW BOILER 1 SET OF BAFFLES 15/21 KW & 21/27 KW BOILERS BOILER SIZE 15/21 KW 21/27 KW 27/38 KW 35/50 KW R/H STACK NO. OF INSERTS FROM L/H SIDE OF CONDENSER 10 15 21 28 35/50 KW BOILER 2 SET OF BAFFLES 8 NO. L/H STACK 7 NO. R/H STACK REMAINING TUBES WITHOUT INSERTS 6 9 12 16 Issue No.1 Combined Manual 24.10.
BURNER SETTINGS BOILER MODEL 15/21 21/27 27/38 35/50 Btu/hr 72000 92000 130000 170000 Kw/hr 21 27 38 50 Btu/hr 63000 82000 113000 160000 Kw/hr 18.5 24 33 46 0.55 80 deg H 0.65 80 deg H 0.85 80 deg H 1.2 80 deg H 8 8 8 8 BURNER AIR SETTING 7 12 15 3.5 SMOKE 0 0 0 0 % 11.
USER INSTRUCTIONS – CONDENSING COMBI BOILERS TIME CLOCK BOILER CONTROL THERMOSTAT CONDENSATE TRAP BOILER OPERATION The Boiler Control Thermostat responds to the temperature of the water within the boiler and switches power to the burner when heat is required. The burner has an independent control system which regulates the firing and (shut-off) of the burner.
BOILER CONTROLS BOILER CONTROL THERMOSTAT The temperature of the water within the boiler and the store is controlled and maintained by the Boiler Control Thermostat located on the boiler control panel. Mixer Valve – the mixer valve can be adjusted to the desired hot water temperature setting, which the householder requires. The valve is graduated between 1 to 5, the greater the number the hotter the water. TEMPERATURE SETTINGS: The Boiler Control Thermostat has a range of 50°C to 80°C.
BUILT IN TIME SWITCH (SENATOR COMBI ONLY) Tappets position Out = On Arrow Manual switch position 1 = On (Top Position) Clock symbol = Timed (centre position) 0 = Off (bottom position) Tappets position In = Off SETTING TIME SWITCH UP The outer dial should be set to the current time. Rotate the dial slowly in a clockwise direction, until the correct hour is approaching the arrow marked on the dial.
SWITCHING THE BOILER OFF The boiler can be switched off by turning the rocker switch, located on the underside of the control panel, to the OFF position. PLEASE NOTE: For longer periods of shutdown e.g. while away on holiday, switch OFF the mains (electrical supply) and turn OFF the OIL supply. If shutdown occurs during cold weather ensure boiler is protected against frost damage.
RESTART - Check there is adequate oil in the storage tank. - Check oil supply valves are open - Switch on heating system (e.g. Time Clock) - Press the Red Burner Reset Button on the burner Control Box, which will be illuminated. Both burner reset button (illuminated) and the lockout indicator on the Control Panel will go out and the burner will commence the ignition start sequence. After 15 seconds the Burner should fire normally.
REGULATIONS The installation of oil-fired boilers should comply with the following standards and codes of practice: - BS5449 Forced circulation hot water heating systems for domestic use. - BS5410-Part 1 Oil installations up to 45kw - BS7593 Water treatment of hot water central heating systems - BS7671 Electrical Regulations - Building Regulations Part 1L and J 2002 England and Wales, Part F Scottish Regulations and Technical Booklet L Northern Ireland.
INSTALLATION SERVICE REQUIREMENTS The boilers are serviced through an access panel at the front. A service access space of at least 700mm should be made available at the front of the boiler. THE HEARTH The temperature of the surface below the boiler is less than 85°C. If the floor under the boiler is of combustible material, then protection such as steel should be fitted between the boiler and the floor.
PREFORMED PIPEWORK - 1 1 1 1 1 of of of of of 22mm 15mm 15mm 15mm 22mm section section section section section labelled labelled labelled labelled labelled Heating Flow Mains Hot Water Overflow Heating Return Preformed pipes, on the senator Combi, can exit on the left or right hand side of the casing. Please ensure that if flueing low level balanced flue from the side of the casing of the boiler, that the preformed pipes are exiting on the opposite side to which the flue is exiting.
CAPACITIES OF EXPANSION VESSELS Safety valve setting @ 3 3 3 Vessel charge and Initial System Pressure (BAR GUAGE) 0.5 1 1.5 LITRES LITRES LITRES LITRES 5 2.1 2.7 3.9 50 4.2 5.4 7.8 75 6.3 8.2 11.7 100 8.3 10.9 15.6 125 10.4 13.6 19.5 150 12.5 16.3 175 14.
CONVENTIONAL FLUE INSTALLATION The boiler is supplied as standard for use with conventional flue. The chimney must comply with building regulations and BS 5410. Factory made insulated chimneys are covered by BS 4543 Parts 2 & 3. Notes on Conventional Flue: 1. Liner – A stainless steel flue liner of diameter to suit the boiler is recommended 2. Flue Pipe – can be of vitreous enamel or stainless steel 3. Bends – Bends in the flue pipe should not be greater than 135 degrees. 4.
ELECTRICAL CONNECTION (SENATOR KITCHEN COMBI) The electrical supply to the boiler must be wired to a double pole - isolating switch 240v/50hz, fused at 5 amps. A multi 3-pin plug is included with the boiler, which connects with the boiler control panel. The burner is supplied with 4-wire cable plug, which allows disconnection for maintenance. CONTROL OPTIONS A Room Thermostat must be fitted for the boiler to work correctly.
ELECTRICAL CONNECTION (COUNTRYMAN OUTDOOR COMBI) The electrical supply to the boiler must be wired to a double pole - isolating switch 240v/50hz, fused at 5 amps. A multi 6-pin plug is included with the boiler, which connects with the boiler control panel. The burner is supplied with 4-wire cable plug, which allows disconnection for maintenance. CONTROL OPTIONS A Room Thermostat must be fitted for the boiler to work correctly.
WIRING DIAGRAM SENATOR COMBI COUNTRYMAN COMBI Issue No.1 Combined Manual 24.10.
COMBI SENATOR KITCHEN MODELS TECHNICAL SPECIFICATION DIMENSIONS A B C D E F G H I J K L M N O 15/21 KW 741 293 140 423 589 641 589 577 614 645 670 705 854 140 240 21/27 KW 741 293 140 423 589 641 589 577 614 645 670 705 854 140 240 27/38 KW 741 293 140 423 589 641 589 577 614 645 670 705 854 140 240 DIMENSIONS ARE IN (mm.) Electrical Supply.
COMBI COUNTRYMAN OUTDOOR MODELS TECHNICAL SPECIFICATION DIMENSIONS A B C D E F G 15/21 KW 645 260 681 868 684 880 827 21/27 KW 645 260 681 868 684 880 827 27/38 KW 645 260 681 868 684 880 827 DIMENSIONS ARE IN (mm) General Data Electrical Supply.
COMMISSIONING & SERVICING INSTRUCTIONS A competent service engineer OFTEC registered should be appointed on an annual basis. • Isolate Power to the boiler • De-pressurise heating system and check expansion vessel pre-charge is the same as the cold fill pressure, of the heating system. Expansion vessel pre-charge must not exceed 1.5 bar.
BOILER WILL NOT START Check if mains electricity supply is reaching boiler control panel, making sure control thermostat is turned on and time clock is calling for heat. Mains indicator green should be illuminated. If green light is not illuminated and fuse has been checked then heating system charge may be low, check black needle on pressure, located inside boiler cabinet (top right hand side) is reading 1 bar or more. If not depressurised, refer to fault diagnosis. FAULT DIAGNOSIS Issue No.
NO HEATING OR HOT WATER - Check there is power to the boiler, has fuse blown? If yes replace and test, if fuse continues to blow check circulation pump is not passing heating water into circulation pump electrical box. Is the system pressure below 1 bar on black needle on pressure gauge? If yes recharge system pressure by opening the filling loop valve slowly, until black needle indicator reads (approx 1 bar) Green neon NOT illuminated. Place rocker switch to the ON position located on the control panel.
SENATOR KITCHEN COMBI PARTS LIST 3 5 7 24 1 8 2 9 4 6 19 10 18 11 16 23 13 17 12 15 14 20 ITEM DESCRIPTION 1 2 3 INTERNAL TIME SWITCH CONTROL THERMOSTAT GREEN NEON ORANGE NEON RED NEON ROCKER SWITCH HIGH LIMIT THERMOSTAT FLOW REGULATOR AIR VENT SAFETY RELIEF VALVE PRESSURE GAUGE GATE VALVES GRUNFOSS PUMP DIVERTER VALVE DIAPHRAGM MIRCO SWITCHES PLATE HEAT EXCHANGER LOW PRESURE SWITCH FILLING LOOP THERMOSTAT MIXER VALVE EXPANSION VESSEL HOSE 12 LITRE EXPANSION VESSEL BURNER DOOR INSULATION