2.1 General Structure and Connection
Figure 1: Dedicated I/O
For three phases supply voltage:
• The circuit breaker current rating should be between 150% to 200%, of the
amplifier’s current.
• The circuit breaker voltage rating should be 460 VAC.
• The contactor should be up to 150% of the amplifier’s current.
For one phase supply voltage:
• The circuit breaker current rating should be between 200% to 300%, of the
amplifier’s current.
• The circuit breaker voltage rating should be 460 VAC.
• The contactor should be up to 200% of the amplifier’s current.