Specifications
-3.5-
SYS 1 SYS 2 SYS 3 DCU OK Code Name
OFF RED RED RED 162 PRC_STATUS_CONFIG_MISSING_IN_FLASH
SYS 1 SYS 2 SYS 3 DCU OK Code Name
GREEN GREEN GREEN RED 086 PRC_STATUS_CONFIG_VDRDEFAULT_ERROR
SYS 1 SYS 2 SYS 3 DCU OK Code Name
GREEN RED GREEN RED 102 PRC_STATUS_CONFIG_UNABLE_TO_SAVE
SYS 1 SYS 2 SYS 3 DCU OK Code Name
RED GREEN OFF RED 026 PRC_STATUS_TIMEDIFF_TOO_BIG
SYS 1 SYS 2 SYS 3 DCU OK Code Name
RED GREEN YELLOW RED 218 PRC_STATUS_MIC_TEST_FAILED
SYS 1 SYS 2 SYS 3 DCU OK Code Name
RED YELLOW YELLOW RED 301-316 PRC_SERIAL_TIMEOUT (250)
Description:
A serial channel has not delivered data within the specified timeout period.
A
ction:
Reconnect serial data.
Check failed device.
Action:
Description:
Microphone test failed to test the microphones defined in the W EB-configurator. This
test can be run from MENU 13 in the WEB-configurator, and is run every 12 hours
during normal operation (first time 12 hours after system start up).
Check if microphones mounted are disabled in the WEB-configurator.
(AUDIO section->channels(3,4,5)).
If this is o.k., locate the faulty microphone and check/replace it.
Description:
Communication-port defined to deliver UTC time information delivered a UTC time that is
more than 1 hour different from the VR-5000 system clock. This normally happens if
GPS or time source sending the information is out of sync, or the system clock wasn’t
set to UTC time before starting.
Action:
Try to see if the CMOS clock is set correctly.
If not, set it and restart VR-5000.
If yes, find out why the time source-device defined in the W EB-configurator is delivering ’
out of bands’ time information.
Description:
VR-5000 could not save configuration to the DRU/BACKUPDRIVE.
Action:
1. Check DRU connected. 2. BACKUPDRIVE O.K. 3. For other call for service.
Description:
Built-in configuration in VR-5000 system software failed to load into the DRU. Reason
can be the firmware itself or a problem with the DRU.
Action:
Clear CONFIG_area and restart VR-5000. This will install a ’default’ minimum
Configuration. If the error still occurs, try to see if the DRU is set up correctly
(partitions/partition-size).
Description:
CONFIG_area in DRU is corrupt/wrong/un-initialized. This should only happen during
installation/service and if using a DRU not initialized by VR-5000 it is connected to.
Action:
Clear CONFIG_area and restart VR-5000. This will install a ’default’ minimum
configuration.