Installation manual

Euphonix CO-600 Change-Over System For New Core DF66 Redundancy
21
Specications
Environmental
The CO-600 shall comply with the environmental operational and storage requirements
as summarized in Table 1: Temperature, Humidity, Sound Level, and Altitude
Requirements.
Temperature, Humidity, Sound Level, and Altitude RequirementsTable 1
Description Operating
Storage
Temperature 0° C 10 +35° C -40° C to +60° C
Temperature Gradient
(Non-condensing)
20° C/hr maximum 40° C-hr maximum
Humidity (Non-condensing)
Maximum Wet Bulb Temperature
20% to 85% RH
29° C
5% to 95% RH
40° C
Sound Level < 50 dBA 0 dBA
Altitude 0 to 10,000 ft above MSL
0 to 50,000 ft above MSL
at -40° C to 70° C
Altitude Gradient 1.5 kPa/min 8 kPa/min
Regulatory
The CO-600 is designed so as not to cause conducted or radiated interference to circuits
internal and external to the unit and so that it is not susceptible to signals generated
internally and externally to the unit.
Emissions
The CO-600 meets the Class A emission limits requirements of both the FCC Part 15 and
EN55103 Part 1 in environments E2 and E4.
Immunity
The CO-600 meets the Class A immunity requirements of both the FCC Part 15 and
EN55103 Part 2 in environments E2 and E4.
Safety
The CO-600 complies with European Standard EN60950 safety standard.
MADI
The CO-600 routes and distributes MADI signals and conforms to the recommended
practice as documented in AES10-2003.