User Manual
Operating Instructions Read Heads/Actuators for Safety Relays ESM
Subject to technical modifications; no responsibility is accepted for the accuracy of this information. © EUCHNER GmbH + Co. KG 096881‑10‑12/13 (translation of the original operating instructions)
Technical data
Parameter Value
Read heads
Housing material Fiber glass reinforced PPS
Ambient temperature ‑20 ... +60 °C
Degree of protection
according to EN 60529
IP 67
Installation position Any, alignment with actuator
should be kept in mind (markings)
Connection Molded cable with crimped fer‑
rules/plug connector M8, 4‑pin/
molded cable with plug connector
M12, 8‑pin
Switching voltage 35 V DC
Switching current I
e
max. 0.1 A
Built‑in fuse 100 mA (per safety contact)
Rated conditional
short‑circuit current
1)
100 A
Contact status indication (only CMS‑R‑AZA)
Switching voltage 35 V DC
Switching current I
e
max. 0.02 A
Switching frequency f
max
at I
min
10 mA
1)
5 Hz
Switching frequency f
max
at nominal current 8 A
1)
0.1 Hz
Switching delay
from state change
1) 2)
26 ms
Method of operation Magnetic, reed contact
Mechanical life 100 x 10
6
operating cycles
Vibration resistance 10 ... 55 Hz, amplitude 1 mm
Shock resistance 30 g/ 11 ms
EMC compliance According to EN 60947‑5‑3
Center offset m from actuator ± 2.5 mm
at a distance of s = 3 mm
Switch‑on distance s
ao
See combination options tableSwitch‑off distance s
ar
Switching contacts
Classification according to EN 60947‑5‑3
CMS‑R‑BZB… M3D36AS1
CMS‑R‑AZA…/CMS‑R‑AZC… M3D88AS1
Fusing of the power supply and the safety contacts
External contact fuse
1)
Fuse 10 A gG
Actuator
Housing material Fiber glass reinforced PPS
Ambient temperature ‑20 ... +60 °C
Degree of protection
according to EN 60529
IP 67
Installation position Any, alignment with read head
should be kept in mind (markings)
Method of operation Magnetic
Vibration resistance 10 ... 55 Hz, amplitude 1 mm
Shock resistance 30 g/ 11 ms
Center offset m
from read head
± 2.5 mm
at a distance of s = 3 mm
Switch‑on distance s
ao
See combination options table
Switch‑off distance s
ar
Reliability values acc. to EN ISO 13849‑1
Category
1)
4
Mission time 20 years
Performance Level
1)
e
B
10d
20 x 10
6
operating cycles
1) Parameter dependent on the evaluation units ESM‑BA2.. and
ESM‑BA3..
2) Corresponds to the risk time according to EN 60947‑5‑3. This
is the maximum switch‑off delay for the safety outputs following
removal of the actuator.
X
Y
Z
Alignment
marking
Approach
direction
X
Y
Z
Approach
direction
Alignment
marking
Design CMS‑.‑A...
Design CMS‑.‑B...
Figure 1: Alignment of read head and actuator
Service and inspection
Remove iron swarf from the read head and actuator
at regular intervals.
Only use solvent‑free detergents for cleaning the
actuators and read heads!
Regular inspection of the following is necessary
to ensure trouble‑free long‑term operation:
f correct switching function
f secure mounting of components
f loose connections.
In the event of damage or wear and tear, the
damaged system component must be replaced.
Exclusion of liability under the following
conditions:
f incorrect use
f non‑compliance with safety regulations
f installation and electrical connection not per‑
formed by authorized personnel
f failure to perform functional checks.