Operating Instructions Non-Contact Safety Switch CES-I-AR-M-C04 (Multicode) More than safety.
Operating Instructions Safety Switch CES-I-AR-M-C04 Contents About this document 3 Correct use Possible combinations for CES components 3 4 Exclusion of liability and warranty 4 General safety instructions 5 Function 6 Mounting 8 Electrical connection Safety in case of faults Fuse protection for power supply Requirements for connection cables Maximum cable lengths Connector assignment, safety switch CES-I-AR Connection of a single CES-I-AR Connection of several CES-I-AR in a switch chain Notes o
Operating Instructions Safety Switch CES-I-AR-M-C04 About this document This document is valid for all safety switches CES-I-AR-M-C04. Correct use The Coded Electronic Safety switches series CES are safety devices for monitoring movable safety guards. In combination with a separating safety guard and the machine control, this safety component prevents dangerous machine movements from occurring while the safety guard is open.
Operating Instructions Safety Switch CES-I-AR-M-C04 Important! ÌÌIn the estimation of the PL for the overall system, a maximum value of 100 years can be assumed for the MTTFd according to the limit value in EN ISO 13849-1:2008, section 4.5.2. This corresponds to a minimum value for the PFHd of 2.47x10-8/h. ÌÌWhen up to 11 devices are connected in series, these limit values can be assumed for the entire switch chain as a subsystem. As a subsystem, this switch chain achieves PL e.
Operating Instructions Safety Switch CES-I-AR-M-C04 General safety instructions Safety switches fulfill personal protection functions. Incorrect installation or tampering can lead to fatal injuries to personnel.
Operating Instructions Safety Switch CES-I-AR-M-C04 Function The device complies with the following safety requirements: ÌÌSafety category 4, PLe according to EN ISO 13849-1 ÌÌRedundant design of the circuit in the unit with self-monitoring ÌÌThis means that the safety system still functions even if an internal component fails ÌÌThe switch state of the semiconductor outputs is continuously monitored internally ÌÌShort circuit detection at the safety outputs by pulsed signals The following switch-on condi
Operating Instructions Safety Switch CES-I-AR-M-C04 The system is designed so that failures will not result in the loss of the safety function. The occurrence of failures is detected by cyclic self-monitoring at the latest on the next demand to switch the safety outputs (e.g. on starting). If the safety door with the actuator should settle over time, the actuator can drift out of the switch operating distance. The device recognizes this situation and indicates that the actuator is in the limit range.
Operating Instructions Safety Switch CES-I-AR-M-C04 Mounting Caution! Risk of damage to equipment as a result of incorrect installation. Safety switches must not be used as a mechanical end stop. ÌÌFit an additional end stop for the movable part of the safety guard. Important! ÌÌFrom the assured switch-off distance Sar, the safety outputs are safely shut down. ÌÌWhen mounting several safety switches and actuators, observe the stipulated minimum distance to avoid mutual interference.
Operating Instructions Safety Switch CES-I-AR-M-C04 Electrical connection The following connection options are available: ÌÌSeparate operation ÌÌSeries connection with Y-distributors from EUCHNER (only with M12 plug connector) ÌÌSeries connection, e.g. with wiring in the control cabinet ÌÌOperation on an AR evaluation unit. Warning! In case of an error, loss of the safety function through incorrect connection. ÌÌTo ensure safety, both safety outputs (FO1A and FO1B) must always be evaluated.
Operating Instructions Safety Switch CES-I-AR-M-C04 Caution! ÌÌIn order to avoid EMC interference, the physical environmental and operating conditions at the installation site of the device must comply with the requirements according to the standard EN 60204-1:2006, section 4.4.2 (EMC). Important! If the device does not appear to function when operating voltage is applied (e.g. green STATE LED does not flash), the safety switch must be returned unopened to the manufacturer.
Operating Instructions Safety Switch CES-I-AR-M-C04 Maximum cable lengths Switch chains are permitted up to a maximum overall cable length of 200 m taking into account the voltage drop as a result of the cable resistance (see table below with example data and case example). lmax =200 m l2 l1 ln un = 24 V -20% umin = 24 V -10% iout SPS PLC 5 x 0,34 mm2 oder 5 x 0,14 mm2 5 x 0,34 mm2 CES-I-AR # n 5 x 0,34 mm2 CES-I-AR # n-1 n Iout (mA) Max.
Operating Instructions Safety Switch CES-I-AR-M-C04 Determining cable lengths using the example table Example: 6 switches are to be used in series. Cabling with a length of 40 m is routed from a safety relay in the control cabinet to the last switch (#6) (conductor cross-section 0.34 mm²). Cables with a length of 20 m each are connected between the individual CES-I-AR safety switches. lmax = 140 m l2 = 5 x 20 m l1 = 40 m ln = 20 m un = min. 19,2 V Sicherheitsrelais iout = min.
Operating Instructions Safety Switch CES-I-AR-M-C04 Connector assignment, safety switch CES-I-AR RST 8 2 7 UB 0V FI1A FO1A FO1B 7 8 6 1 FI1B OD 6 5 4 1 3 4 5 Coding lug 2 3 View on the connection side of the safety switch Figure 2: Connector assignment, safety switch CES-I-AR Pin Designation Description 1 FI1B Enable input for channel 2 Wire color white 2 UB Power supply, DC 24 V brown 3 FO1A Safety output, channel 1 green 4 FO1B Safety output, channel 2 yellow gray 5 OD
Operating Instructions Safety Switch CES-I-AR-M-C04 Connection of a single CES-I-AR If a single CES-I-AR is used, connect the switch as shown in Figure 3. The OD output can also be connected here to a control system as a monitoring output. The switch can be reset via the RST input. To do this, a voltage of 24 V is applied to the RST input for at least 3 seconds. The RST input must be connected to 0 V if it is not used. Important! The subsystem CES-I-AR complies with PL e in accordance with EN 13849-1.
Operating Instructions Safety Switch CES-I-AR-M-C04 Warning! In case of an error, loss of the safety function through incorrect connection. ÌÌTo ensure safety, both safety outputs (FO1A and FO1B) must always be evaluated. Single-channel use of the safety outputs leads to a loss of the category in accordance with EN ISO 13849-1.
Operating Instructions Safety Switch CES-I-AR-M-C04 Connection of several CES-I-AR in a switch chain Important! ÌÌAn AR switch chain may contain a maximum of 20 safety switches. ÌÌIn the estimation of the PL for the overall system, a maximum value of 100 years can be assumed for the MTTFd according to the limit value in EN ISO 13849-1:2008, section 4.5.2. This corresponds to a minimum value for the PFHd of 2.47x10-8/h.
Terminating plug 17 FI1B 6 FI1A Safety Inputs 1 8 RST Y-distributor 5 2 UB 7 0V 4 FO1B 5 OD 3 3 FO1A CES Safety Outputs OD FI1B 6 FI1A Safety Inputs 1 8 RST 2 UB 7 0V Y-distributor 4 FO1B CES Safety Outputs FO1A FI1B 1 6 8 2 7 5 3 4 FI1A 4 4 FO1B 4 FI1B 0V 2 2 FO1A 3 3 0V 2 UB 1 FI1A RST 5 1 5 UB Read Head 1 Read Head RST Y-distributor FI1B FI1A RST UB 0V OD FO1A FO1B UB Terminating plug FI1B 6 FI1A Safety Inputs 1 8 RST 2 UB
Operating Instructions Safety Switch CES-I-AR-M-C04 Notes on operation with safe control systems Please observe the following requirements for connection to safe control systems: ÌÌUse a common power supply for the control system and the connected safety switches. ÌÌA pulsed power supply must not be used for UB. Tap the supply voltage directly from the power supply unit. If the supply voltage is connected to a terminal of a safe control system, this output must provide sufficient electrical current.
Terminating plug 19 FI1B 6 FI1A 8 Safety Inputs 1 RST 2 UB 7 0V Y-distributor 3 FO1A 4 FO1B Safety Output OD CES 5 FI1B 6 FI1A 8 RST Safety Inputs 1 2 UB 7 0V Y-distributor 5 3 FO1A 4 FO1B CES Safety Output OD 1 IA RST 6 8 2 Safety Inputs IB UB 7 0V Y-distributor 5 OA OB LED1 UCM J 0V(UCM) CET 3 4 X2:3 X2:4 X2:5 X2:1 Safety Output OUT -X1 ET200 4 F-DO DO..M DO..
Operating Instructions Safety Switch CES-I-AR-M-C04 Setup LED indicators LED STATE DIA Color State Significance illuminated Normal operation: Door closed flashing - Power Up - Door open - Actuator in the limit range (refer to the status table for further signal functions) illuminated - Internal electronics fault - Fault at the inputs/outputs green red Initial setup 1. Apply operating voltage to the safety switch. ¨¨ The green LED flashes quickly (approx. 5 Hz).
Operating Instructions Safety Switch CES-I-AR-M-C04 System status table X off off closed on on closed on on flashing quickly closed off on 1 x inverse open off off 1x Normal operation, door open open off off 2x Normal operation, door open, no actuator taught X off off 2x Input fault (e.g. missing test pulses, illogical switch state from previous switch in the switch chain) closed off off 3x Defective actuator (e.g.
Operating Instructions Safety Switch CES-I-AR-M-C04 Technical data Note! If a product data sheet is included with the product, the information on the data sheet applies in case of discrepancies with the operating instructions. Technical data for safety switch CES-I-AR-M-C04 Parameter Value typ. max. Plastic PBT 42 x 25 x 18 0.05 -25 + 65 - Plug connector M8, 8-pin or - Connection cable PUR, 0.14 mm², with plug connector M12, 8-pin, or - Connection cable PUR with flying lead, 8 x 0.
Operating Instructions Safety Switch CES-I-AR-M-C04 Typical system times Ready delay: After switching on, the unit carries out a self-test for 8 s. The system is ready for operation only after this time. Switch-on time of safety outputs: The max. reaction time from the moment when the actuator is at the operating distance (safety door closed) to the moment when the safety outputs switch on Ton is 300 ms (400 ms for switch chains).
Operating Instructions Safety Switch CES-I-AR-M-C04 Dimension drawings Connection cable with M12 plug connector M12x1 ca.
Operating Instructions Safety Switch CES-I-AR-M-C04 Connector assignment for safety switch CES-I-AR (8-pin plug) and Y-distributor (8-pin socket) Bridging plug 097645 4-pin, plug Pin Function 1 FI1B 2 UB 3 FO1A 4 FO1B 5 OD 6 FI1A 7 0V 8 RST Y-distributor with connection cable 111696 or 112395 Y-distributor 097627 Socket 2 3 4 5 Socket 2 3 1 6 4 5 8 15,1 6 1 8 ( 45 °) M12x1 M12x1 M 12x1 Length l 41 15 45 15 max. 45 7 7 M 12x1 Ø 14,5 Order no.
Operating Instructions Safety Switch CES-I-AR-M-C04 Technical data for actuator CES-A-BBN-C04 Parameter Value min. Unit typ. Housing material max. Plastic PBT Dimensions Mass Ambient temperature - 40 42 x 25 x 18 mm 0.
Operating Instructions Safety Switch CES-I-AR-M-C04 Operating distances Operating distance for center offset m = 0 (only in combination with actuator CES-A-BBN-C04 from approach direction A or B) Approach direction A B Parameter Value Switch-on distance Unit min. typ. max.
Operating Instructions Safety Switch CES-I-AR-M-C04 Technical data for actuator CES-A-BDN-06 Parameter Value min. Unit typ. Housing material max. Macromelt PA-based plastic Dimensions 26 x ∅ 6 mm 0.005 kg Mass Ambient temperature - 40 - Degree of protection + 70 °C IP67 / IP69K 1) Installation position Active face opposite read head Power supply Inductive via read head 1) With flush installation Dimension drawing Installation options 6 Operating distance Ø 30 * min.
Operating Instructions Safety Switch CES-I-AR-M-C04 Ordering information and accessories Designation Version Order no. CES-I-AR-M-C04-U05-119475 Safety switch, multicode, connection cable PUR 5 m, flying lead 8 x 0.14 mm² 119475 CES-I-AR-M-C04-U10-119476 Safety switch, multicode, connection cable PUR 10 m, flying lead 8 x 0.14 mm² 119476 CES-I-AR-M-C04-U20-119477 Safety switch, multicode, connection cable PUR 20 m, flying lead 8 x 0.
Operating Instructions Safety Switch CES-I-AR-M-C04 Service If service support is required, please contact: EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Service telephone: +49 711 7597-500 E-mail: info@euchner.de Internet: www.euchner.
Operating Instructions Safety Switch CES-I-AR-M-C04 Declaration of conformity 31
Operating Instructions Safety Switch CES-I-AR-M-C04 32
Operating Instructions Safety Switch CES-I-AR-M-C04 33
Euchner GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen info@euchner.de www.euchner.de Edition: 119562-04-05/14 Title: Operating Instructions Safety Switch CES-I-AR-M-C04 (translation of the original operating instructions) Copyright: © EUCHNER GmbH + Co. KG, 05/2014 Subject to technical modifications; no responsibility is accepted for the accuracy of this information. More than safety.