Operating Instructions Safety Switches CES-AR-C.2-CH
22
System status table
Operating mode
Actuator/
door position
Safety outputs
OA and OB
Monitoring output
OUT
LED indicator
output
State
STATE (green)
DIA (red)
Self-test
X off off
10 Hz 
(8 s)
Self-test after power up
Normal operation
closed on on
Normal operation, door closed
closed On on
flashes 
quickly
2 Hz
Normal operation, door closed, actuator in the boundary area ¨ Re-adjust door (V. 1.1.2 
or higher)
closed off on
1 x 
inverse
Normal operation, door closed, preceding device in the switch chain signals "door open" 
(only with series connection)
open off off
1 x Normal operation, door open
Fault display
X off off
2 x
Input fault (e. g. missing test pulses, illogical switch state from previous switch in the 
switch chain)
X off off
4 x Output fault (e. g. short circuits, loss of switching ability)
X off off
5 x Internal fault (e.g. component faulty, data error)
X off off X X Internal fault with door fault
Key to symbols
LED not illuminated
LED illuminated
10 Hz (8 s)
LED flashes for 8 seconds at 10 Hz
3 x
LED flashes three times, and this is then repeated
X Any state
After the cause has been remedied, faults can generally be reset by opening and 
closing the door. If the fault is still displayed afterward, use the reset function or 
briefly interruptthe powersupply. Please contact the manufacturerif the fault could 
not be reset after restarting.
Important!
If you do not find the displayed device status in the System status table, this indi-
cates an internal device fault. In this case, you should contact the manufacturer.