Manual

Operating Instructions AR Evaluation Unit CES-AR-AES-12
17
System status table
Operating mode
Actuator/
guard position
Safety outputs
OA and OB
Indicator LEDs
Door monitor-
ing outputs
State
DIA (red)
OUT (yel-
low)
STATE
(green)
OUT AR
DIA
Self-test
X off
15 Hz 
(8 s)
off off Self-test after power up
Normal operation
open off
off off Normal operation, at least one door open
closed On
On off Normal operation, all doors closed
closed off
3 Hz On off
Normal operation, all doors closed, start button not 
pressed or fault in the feedback loop
closed off
4 x On On
Normal operation, all doors closed, feedback loop 
was open during attempt to start
X X
X 7 x off On
Faulty data transmission for status signals (safety 
circuit not affected)
Fault display
X off
1 x off On
Fault in the AR switch chain (e.g. fault on starting the 
switch chain or more than 12 devices connected)
X off
2 x off On
Fault on the safety outputs or on the start button 
(e.g. start configuration changed in operation, no/
erroneous signals from the switch chain, broken 
cable on one of the channels I
A
 or I
B
, or short circuit/
ground fault on one of the cables I
A
 or I
B
)
X off
4 x off On
Fault on the safety relay, re-start device. 
If fault is still indicated, contact manufacturer.
X off
5 x off On
Internal component fault, re-start device. 
If fault is still indicated, contact manufacturer.
X off
6 x off On
-Fault in feedback loop, 
e.g. 
-
feedback loop not connected on power up
-missing jumper between Y1/Y2
or
-Fault in the start button, 
e.g. 
-on autostart: jumper between S/U
B
 instead of S/
Y1
-Start button stuck
X off
off On Start failed three times, contact manufacturer
Key to symbols
LED not illuminated
LED illuminated
15 Hz (8 s)
LED flashes for 8 seconds at 15 Hz
3 x
LED flashes three times
X Any state