If a feedback loop is not to be connected, a jumper must be fitted to the terminals 
Y1 and Y2 (see Figure 7).  
CES-AR-AES
33
43
23
13
Y2
Y1
24 34 44
14
+24 V
Subsequent
devices
(e.g. contactors)
Fig. 7: Safety contacts connected and jumper on the feedback loop
The following conditions must be met for the safety contacts to be closed:
For manual start
Ì The feedback loop is closed 
Ì The start button has been pressed and released (switches on falling edge)
Ì All safety doors closed
For automatic start
Ì The feedback loop is closed
Ì All safety doors closed
If the feedback loop is open, theDIALED flashes and the STATELED is lit (see 
section Troubleshooting). The monitoring output DIA is set.
The safety contacts remain open if the feedback loop is open at the start. The unit 
switches to fault state, the  DIA LED illuminates, and the STATE LED flashes (see 
section Troubleshooting).