Technical Data
Parameter
Value
Unit
min. typ. max.
Housing material Plastic PBT V0 GF30
Dimensions According to EN 60947-5-2 mm
Weight 0,4 kg
Ambient temperature at U
B
= DC 24 V -20 - +55 °C
Degree of protection IP67
Degree of contamination 3
Rated insulation voltage U
i
- - 300
1)
V
Rated impulse withstand voltage U
imp
- - 1,5 kV
Rated conditional short-circuit current 100 A
Resilience to vibration According to EN 60947-5-2
Installation position Any
Connection type M12 plug connector, 8-pin, screen can be applied
Operating voltage U
B
(regulated, residual ripple < 5 %) 18 24 27 V DC
For the approval according to UL the following applies Operation only with UL Class 2 power supply, or equivalent measures
Current consumption 80 mA
Switching load according to UL max. DC 24 V, class 2
External fuse (operating voltage U
B
) 0,25 - 8 A
Power supply for load U(+LA)/U(+LB) 18 - 27 V DC
Safety outputs (LA / LB, 2 semiconductor outputs, p-switch
-
ing, short circuit-proof, electrically decoupled)
- Output voltage U(LA/U(LB)
2)
HIGH U(LA) U(+LA) - 1.5 - U(+LA)
HIGH U(LB)
U(+LB) - 1.5 - U(+LB) V DC
LOW U(LA)/U(LB)
0 - 1
Switching current per safety output 1 - 400 mA
External fuse (U(+LA)/U(+LB), safety circuit 400 mA medium slow-blow
Utilization category to EN 60947-5-2 DC-13 24V 400mA
Classification according to EN 60947-5-3 PDF-M
Door monitoring output (OUT, semiconductor output, p-
switching, short circuit-proof)
- Output voltage 0.8 x U
B
- U
B
V DC
- Max. load - - 20 mA
Switching delay from state change
3)
- - 180 ms
Discrepancy times of both safety outputs - - 120 ms
Ready delay
4)
- - 3 s
Dwell time
5)
0,5 - - s
Switching frequency - - 1 Hz
Repeat accuracy R according to EN IEC 60947-5-3 ≤ 10 %
Mounting distance between 2 read heads or 2 actuators
80 - - mm
EMC protection requirements In acc. with EN 60947-5-3
LED displays STATE Green LED: Normal operation
Flashing: Teach-in operation
OUT/ERROR Yellow LED: Actuator detected
OUT/ERROR Red LED: - EMC interference
- Internal electronics fault
- Invalid teach-in operation
Reliability figures according to EN ISO 13849-1 CES-A-C5E-... CES-A-C5H-...
Category 3 4
Performance Level (PL) PL e PL e
PFH
d
4.29 x 10
-8
/ h 3.7 x 10
-9
/ h
6)
Mission time 20 20 years
1) Tested by BG up to 75 V.
2) Values at a switching current of 50 mA without taking into account the cable lengths.
3) Corresponds to the risk time according to EN 60947-5-3. This is the maximum switch-off delay for the safety outputs following removal of the actuator.
4) After the operating voltage is switched on, the semiconductor outputs are switched off and the monitoring outputs are set LOW during the ready delay.
5) The dwell time of an actuator inside and outside the operating distance must be at least 0.5 s to ensure reliable detection of internal faults in the evaluation unit (self-monitoring).
6) Applying the limit value from EN ISO 13849-1:2008, section 4.5.2 (MTTF
d
= max. 100 years), BG certifies a PFH
d
of max. 2.47 x 10
-8
.
Ordering table
Series Category according to EN ISO 13849-1 Order no. / item
CES-A-C5...
3
077750
CES-A-C5E-01
4
5)
091458
CES-A-C5H-01
5) Category 4 according to EN 13849-1 for monitoring short circuits of safety outputs. A short circuit between LA and LB must be detected by external pulsing or must be excluded by laying
the cable with protection.