5. Installation
5.1 Dimensions
5.2 Connections
Warning!
Cover the top of the AS-I Safety Monitor when doing any drilling work above the unit.
No particles, especially metal chips, should be allowed to enter the housing, since this
could cause a short circuit.
Information!
For additional information, please refer to <Section 15 “Appendix: Installation Notes”>.
5 ... 6 mm / PZ2
0,8 Nm
7 LB.IN
2 x (0,5 .... 1,5) mm
2
2 x (0,5 ..
.. 1,5) mm
2
AWG 2 x 24 ...12
10
10
Attention!
The AS-I power supply for the AS-I components must have isolation per IEC 60
742 and be able to handle momentary power interruptions of up to 20 ms. The
power supply for the 24 V supply must also have isolation per IEC 60 742 and be
able to handle momentary power interruptions of up to 20 ms. The maximum out-
put voltage of the power supply must also be less than 42 V in case of a fault.