Safety Monitor for 2 AS-i circuits Instruction Manual

88
Subject to reasonable modifications due to technical advances Id.-No.: 103329 Issue date - 24.10.2008 EUCHNER GmbH + Co. KG
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 • Fax. +49/711/753316
AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor
Operation in advanced display mod
9.6.1 AS-I CIRCUIT (Selecting the AS-i circuit)
Main Menu || DIAGNOSIS || SAFETY SLAVES || AS-I CIRCUIT ||
Please select the required AS-i circuit using the arrow buttons and the OK button.
Than you get the diagnostic menu.
9.6.2 SAFETY SLAVES (safety oriented slaves)
Main Menu|| DIAGNOSIS || SAFETY SLAVES || SAFETY ORIENTED SLAVES ||
The list of “Safety Input Slaves” (“AS-i Safety at Work”) shows the slaves for
which the safety function has been released:
The first place corresponds to Channel 2, the second place to Channel 1. Thus
RX means that Channel 2 released and Channel 1 is OK.
The channels can not be evaluated individually, if the substitution of safety slaves
input data was disabled in menu:
• command interface/ function profile
or
• slave value substitute (SAFETY SUBST VALUE).
In this case both channels must have the same state, otherwise the indication will
not be proper.
AS-I CIRCUIT 1
AS-i CIRCUIT 2
SAFETY ORIENTED
SLAVES
| 1-XX
2-XR
| 3-RR
4- | 5-
X: The channel is OK
R: The channel has released