Safety Monitor for 2 AS-i circuits Instruction Manual
AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor
Spezifications
Subject to reasonable modifications due to technical advances Id.-No.: 103329 Issue date - 24.10.2008 EUCHNER GmbH + Co. KG
23
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 • Fax. +49/711/753316
103374
4 x LED output circuit state of output circuit
LED off: open
LED on: closed
Electrical data
Operating current master power supply, approx. 300 mA out of the AS-i network 1,
approx 70 mA out of the AS-i network 2
Operating voltage AS-i voltage 30 V
DC
24 V
DC
for the outputs K3, K4
Voltage of insulation t 500 V
Standards EN 61 000-6-2, EN 61 000-6-4
EN 62 061, SIL3
EN 61 508, SIL3
EN 13 849, performance level e
Housing AS-i master housing in stainless steel
Ambient operating temperature 0°C … +55°C
Storage temperature -25°C … +85°C
Dimensions (L / W / H in mm) 120 / 100 / 96
Protection category IEC 60 529 IP20
Tolerable loading referring to impacts
and vibrations
according to EN 61 131-2
Weight 800 g
Safety Monitor block diagram: Connections:
Sicherheitsmonitor
(Safety Monitor)
1.Y1 (EDM 1 / Start 1)
2.Y1 (EDM 2 / Start 2)
1.Y2 (EDM 3 / Start 3)
2.Y2 (EDM 4 / Start 4)
1.13 1.14
2.13
2.14
Eingänge
(Inputs)
Freigabe
(Release)
0 V
4.14
24 V
3.14
Freigabe
(Release)
Freigabe
(Release)
Freigabe
(Release)
Freigabe
(Release)
Freigabe
(Release)
Freigabe
(Release)
Freigabe
(Release)
+
-
+
-
+
-
+
PROFIBUS
2.13
+
24 V
2.Y1
0 V
+
1.13
2.Y2
1.Y2
2.14
+
4.14
+
1.14
1.Y1
3.14
+ ASI 2 –
+ASI 1–
+
-
ASI 1 +PWR- (max. 8A)
ASI 2 +PWR- (max. 8A)
Gateway + Safety Monitor
output switching elements
EDM/START inputs
EDM/START inputs
output switching elements