Safety Monitor for 2 AS-i circuits Instruction Manual

22
Subject to reasonable modifications due to technical advances Id.-No.: 103329 Issue date - 24.10.2008 EUCHNER GmbH + Co. KG
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 • Fax. +49/711/753316
AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor
Spezifications
4.1.3 Data sheet 103374
103374
PROFIBUS interface according to DIN 19 245, part 3
Baud rates 9,6 kBaud up to 12000 kBaud, automatic recognition
DP functions imaging of the AS-i slaves as I/O data of the PROFIBUS
complete diagnosis and configuration via the PROFIBUS DP
Serial interface RS 232
AS-i cycle time 150 Ps
*
(number of slaves + 2)
Safety monitor
Release circuit 4-channel
Start delay < 10 s
Respond delay < 40 ms
Inputs:
4 x EDM/Start
EDM: inputs of external device monitoring circuits
Start: Start inputs
switching current statical 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 µs)
Outputs:
4 x output switching elements
relay outputs (output circuits 1 and 2)
max. contact load: 3 A AC-15 at 30 V, 3 A DC-13 at 30 V
semiconductor outputs (output circuits 3 and 4)
max. contact load: 0,5 A DC-13 at 30 V
Card slot chip card for storage of configuration data
Displays
LCD indication of slave adresses and error messages
LED power power on
LED PROFIBUS PROFIBUS master recognized
LED config error configuration error
LED U AS-i AS-i voltage OK
LED AS-i active AS-i normal operation active
LED prg enable automatic addresses programming enabled
LED prj mode configuration mode active
LED AUX auxiliary power
4 x LED EDM/Start state of input of ext. device monitoring circuit
LED off: open
LED on: closed