17.2.3 Configuring AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor
in-/output
If the AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor is added to the
PROFIBUS using drag and drop, the Step7 hardware configuration shows the fol-
lowing graphic.
At this point the desired PROFIBUS communication module should be parame-
terrised. This is done in the following steps:
1. Select the AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor by
clicking on the Slave icon. In the lower edge of the screen a table is shown
which contains lines beginning with Slot 0.
2. Select the desired communication module "Flags + Fault Detector" from the
hardware catalog. These flags use the individual bits to signal the operating
status of the AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor
and should be processed in the application program.