11.1.3 I/O Data
11.1.3.1 Process data
Process data is arranged the same as for the Siemens and AS-i/InterBus mas-
ters. Therefore, data for slaves with a higher address are transmitted in a least
significant nibble. Additionally, the EC-flags or hi-flags, respectively, are placed
at the data location of AS-i slave 0.
2.Modul parameter erquired
Length
1
description
2 byte I flags and AS-i detector
Tab. 11-17.
1.Possible for 2 circuits
Length description
2 byte I / 1 byte O safety control / status
Tab. 11-18.
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0 Flags Slave 1/1A
F3 F2 F1 F0 D3 D2 D1 D0
1 Slave 2/2A Slave 3/3A
2 Slave 4/4A Slave 5/5A
3 Slave 6/6A Slave 7/7A
4 Slave 8/8A Slave 9/9A
5 Slave 10/10A Slave 11/11A
6 Slave 12/12A Slave 13/13A
7 Slave 14/14A Slave 15/15A
8 Slave 16/16A Slave 17/17A
9 Slave 18/18A Slave 19/19A
10 Slave 20/20A Slave 21/21A
11 Slave 22/22A Slave 23/23A
12 Slave 24/24A Slave 25/25A
13 Slave 26/26A Slave 27/27A
14 Slave 28/28A Slave 2929A
15 Slave 30/30A Slave 31/31A
16 reserved Slave 1B
17 Slave 2B Slave 3B
18 Slave 4B Slave 5B
19 Slave 6B Slave 7B
20 Slave 8B Slave 9B