Safety Monitor for 2 AS-i circuits Instruction Manual

AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor
Operation in advanced display mod
Subject to reasonable modifications due to technical advances Id.-No.: 103329 Issue date - 24.10.2008 EUCHNER GmbH + Co. KG
111
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 • Fax. +49/711/753316
Procedure:
1. Store AS-i configuration in the device. This can easily be done by using the
Windows software AS-i Control Tools (Master | Store configuration for the
AS-i Master ...), or directly in the advanced display mode.
2. All AS-i slaves have to be addressed to 0 or to the desired address. The
slaves must be disconnected from the AS-i network.
3. Start the AS-i address assistant.
4. Now the AS-i slaves are connected to the AS-i network one at the time in
the order specified by the AS-i address assistant. The last line displayed for
the AS-i address assistant shows which AS-i slave will be connected next.
9.9.7 AS-I CONTROL (Optional)
Main menu || SETUP || AS-I CONTROL ||
9.9.7.1 CONTROL INFO (Status of the control program)
Main menu || SETUP || AS-I CONTROL || CONTROL INFO ||
This function displays the current status of the AS-i control (control program).
ASSISTANT ON: AS-i address assistant is switched on.
ASSISTANT OFF: AS-i address assistant is switched off.
CONTROL INFO
CONTROL RUN
CONTROL FLAGS
CONTROL INFO
START BIT SET
RUNNING
CYCLE TIME
ACT: 2MS
MAX: 5MS
START BIT SET: The control program has been started.
START BIT RESET: The control program has been stopped.
RUNNING: The control program is running.
STOPPED: The control program has stopped. If, for instances, a configu-
ration error occurs or if the master is in the configuration mode,
the control program can be stopped even if the start bit is set.
CYCLE TIME ACT: Current cycle time of the control program.
CYCLE TIME MAX: Maximum cycle time of the control program since its last start.