Safety Monitor for 2 AS-i circuits Instruction Manual

110
Subject to reasonable modifications due to technical advances Id.-No.: 103329 Issue date - 24.10.2008 EUCHNER GmbH + Co. KG
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 • Fax. +49/711/753316
AS-i 3.0 PROFIBUS Gateway with integrated Safety Monitor
Operation in advanced display mod
9.9.4 FORCE OFFLINE (Switch AS-i Master to offline operation)
Main menu || SETUP || FORCE OFFLINE ||
This function is used to change the address of a slave.
With "Change", this status can be changed.
Switching the AS-i master to offline operation puts the AS-i network into the safe
state. The AS-i master must be offline if an AS-i slave needs to be readdressed
via the IR-interface.
9.9.5 AUTO ADDR ENABLE (enable automatic address)
Main menu || SETUP || AUTO ADDRESS ||
This function is used to enable or disable automatic single node address assign-
ment. This mode can be:
With "Change" the operation can be changed.
9.9.6 AS-I ADDRESS (AS-i address assistant)
Main menu || SETUP || AS-I ADDRESS ||
The AS-i address assistant assists the user to quickly set up an AS-i network.
Once the AS-i configuration has been stored, a new AS-i slave with address 0
can be used to assign the correct address.
Selecting "Assistant on" or "Assistant off" switches the AS-i address assistant on
or off. The current state of the AS-i address assistant is displayed:
FORCE OFFLINE
NO
CHANGE
YES: AS-i Master is offline.
NO: AS-i Master is online.
AUTO ADDRESS
ENABLE
CHANGE
Enable: Automatic address assignment is released
Disable: Automatic address assignment is locked
AS-I ADDRESS
ASSISTANT ON
NEXT ADDRESS TO
PROGRAM 1A