Operating Instructions
Operating Instructions
Key Adapter CKS2-K-BP/BR-CC-FLX
18
(translation of the original operating instructions) MAN20001512-01-03/22
10.2. Series connection with Y-distributors
The series connection is shown here based on the example of the version with plug connector M12. The key adapters are
connected one behind the other with the aid of pre-assembled connecting cables and Y-distributors. The safety outputs are
switched off if the key is removed from the key adapter or if an error occurs on one of the key adapters.
10.2.1. Maximum cable lengths
Important!
The maximum number of devices in a BR switch chain depends on many factors, including the cable
length. This case example shows a standard application. You will nd further connection examples at
www.euchner.com.
SPS
PLC
l
1
l
2
l
max
=200 m
l
n
u
min
= 24 V
5 x 0,34 mm
2
5 x 0,34 mm
2
5 x 0,34 mm
2
CKS2-K-BR # n CKS2-K-BR # n-1 CKS2-K-BR # 1
i
out
n
Max. number of devices
depending on the cable length
I
FO1A
/I
FO1B
(mA)
Possible output current
per channel FO1A/FO1B
l
1
(m)
Max. cable length f
rom the last key adapter to the control system
0.34 mm²
5
10 100
25 100
50 80
100 50
200 25
6
10 100
25 90
50 70
100 50
200 25
10
10 70
25 60
50 50
100 35
200 20