8.4. Requirements for connecting cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connecting cables.
Ì Use connection components and connecting cables from EUCHNER.
Ì On the use of other connection components, the requirements in the following table apply. EUCHNER
provides no warranty for safe function in case of failure to comply with these requirements.
Observe the following requirements with respect to the connecting cables:
Parameter Value Unit
Conductor cross-section, min. 0.25 … 0.34 mm²
R max. 80 W/km
C max. 120 nF/km
L max. 0.65 mH/km
Recommended cable type
5-pin 5 x 0.34mm²
8-pin LIYY 8 x 0.34mm²
8.5. Connector assignment of key adapter CKS2-K-BR-CC-FLX-F00-USA-…
with plug connector M12, 8-pin
Plug connector
(view of connection side)
Pin Designation Function
Conductor coloring
of connecting
cable
1)
21
4
3
8
5
6
7
1 FI1B Enable input, channelB WH
2 UB Operating voltage, 24VDC BN
3 FO1A Safety output, channelA GN
4 FO1B Safety output, channelB YE
5 OD/C Monitoring output/communication GY
6 FI1A Enable input, channelA PK
7 0V Ground 0VDC BU
8 - n.c. RD
1) Only for standard EUCHNERconnecting cable
8.6. Connector assignment of key adapter CKS2-K-BP-CC-FLX-F00-USI-…
with plug connector M12, 5-pin
Plug connector
(view of connection side)
Pin Designation Function
Conductor coloring
of connecting
cable
1)
1
4
3
2
5
1 UB Operating voltage, 24VDC BN
2 FO1A Safety output, channelA WH
3 0V Ground 0VDC BU
4 FO1B Safety output, channelB BK
5 - n.c. GY
1) Only for standard EUCHNERconnecting cable