The data structure of selection of operating mode is hierarchically structured for the individual authorization levels, and it
changes values accordingly in the individual polling levels.
MSO1 MSO3 MSO4
MSO SE
MSO2
0FF0H 3333H 33CCH
3C3CH
0F0FH
MSO1 MSO3 MSO4
MSO SE
MSO2
MSO1 MSO3 MSO4
MSO SE
MSO2
3333H 33CCH 3C3CH
0F0FH
0FF0H
33CCH 3C3CH 0F0FH
0FF0H
3333H
MSO1 MSO3 MSO4
MSO SE
MSO2
0F0FH 0FF0H 3333H
33CCH
3C3CH
Setting outputs to safe control system
Selecting operating mode
Checking selection
Conrming selected operating mode
Fig. 2: Data structure of selection of operating mode
To fulll the safety function of the overall selection of operating mode system, a suitable activation system must be connected
to the safe outputs of the device. A suitable activation system is a safe control system that can process 1-of-n signals, for
example.
The failure probability of the overall system’s safety function can therefore be calculated as follows:
PFH
D,tot.
= PFH
D,EKS2
+ PFH
D,Control
EKS2
PFH
D,EKS2
PFH
D,Control
HMI
touch panel
Access system
Activation system,
e.g. control system
Selection system
1 of n